Siemens FUS1010 Operating Instructions Manual page 115

Sitrans standard liquid ultrasonic flow meter
Hide thumbs Also See for FUS1010:
Table of Contents

Advertisement

Functions
7.4 Span Data
To change the default Span Data settings:
1. At [Meter Type], press <Right Arrow> to [Dual Path Flow] and press <ENTER>.
2. Scroll to [Span/Set/Cal] and press <Right Arrow>.
3. Highlight [Span Data] and press the <Right Arrow>.
4. Highlight [Max Flow] and press <Right Arrow> to. Input 100% flow rate numeric data for
5. Scroll down to [Min Flow].Press <Right Arrow> to input 0% flow rate numeric data for
114
20mA. Press <ENTER> to store data.
4mA. Press <ENTER> to store data.
Input numeric flow data here
FUS1010 IP65 NEMA 4X & IP66 NEMA 7
Operating Instructions, 01/2013, A5E02951520-AC