WAGO-I/O-SYSTEM 750
750-630 SSI Transmitter Interface

Table 16: Status Byte S0 (variants 750-630/000-004, /000-005 and /000-007 only)

Bit 7
0
ERROR
FRAME_E
SSI_IN_E
0
Pos: 35 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.2.0, valid from FW/HW-Version 3A/05
Bit 6
Bit 5
ERROR
0
A general error has occurred. This bit is set if a FRAME or SSI IN error has
occurred.
An incorrect data frame exists, i.e. the data frame is not terminated with zero
(possible wire break of clock lines).
The SSI input of the I/O module is at low level if there is no data transmission.
Possible causes are:
SSI has no power supply
Wire break on SSI data inputs +D or -D
Data lines switched
reserved
Bit 4
Bit 3
0
0
Process Image
Bit 2
Bit 1
FRAME_
0
SSI_IN_E
E