Table 13: Selection Boxes for the Parameterization Dialog

Selection box
Baud rate
PI Length
Var. Frame Length***
Output Format
Synchronous Operation
Gray-Dualcode
Conversion
Single-Turn Evaluation
Frame Error
Power Fail Bit
(PFB)
* Default settings
** At 1 MHz max. 8 bit possible
*** Only adjustable at 125 kHz
Pos: 31 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.2.0, valid from FW/HW-Version 3A/05
Possible settings
1.0 MHz** / 250.0 kHz / 125.0 kHz* / 100.0 kHz /
83.0 kHz / 71.0 kHz / 62.5 kHz
0 bit ... 24 bit* ... 32 bit (numeric input field)
Not used*
Variable data frame disabled
1 bit / ... /
Length of the variable data frame for
32 bit
data exchange between the I/O
module and SSI absolute encoder
Default
(see mapping tables in the fieldbus
coupler/controller manuals)
Alternative*
(see mapping tables in the fieldbus
coupler/controller manuals)
Disable*
Synchronous operating mode of the
SSI absolute encoder disabled
Enable
Synchronous operating mode of the
SSI absolute encoder enabled
Data transmission is synchronous with
the read cycle of the I/O module.
Disable
Gray-dualcode conversion disabled
Enable*
Gray-dualcode conversion enabled
Disable*
Single-turn evaluation disabled
Enable
Single-turn evaluation enabled
(13 bit)
Disable
Frame error disabled
Enable*
Frame error enabled
Disable*
Power fail bit disabled
Enable
Whether the data line sends a zero
signal after the last valid bit.
Commissioning
33