7. Troubleshooting

7.1 Common problems
Television interference: Operation of the power inverter can interfere with television
reception on some channels. If this situation occurs, the following steps may help to
alleviate the problem:
Make sure that the chassis ground lug on the back of the power inverter is solidly
connected to the ground system of your vehicle, boat or home.
Do not operate high power loads with the power inverter while watching television.
Make sure that the antenna feeding your television provides an adequate ("snow
free") signal and that you are using good quality cable between the antenna and the
TV.
Move the television as far away from the power inverter as possible.
Keep the cables between the battery and the power inverter as short as possible
and twist them together with about two to three twists per foot. This minimizes
radiated interference from the cables.
7.2 Troubleshooting guide
Problem and Symptoms
No output voltage, no voltage
indication.
No output voltage, Over Voltage
indicator on
Low battery alarm on all the time.
No output voltage and Under Voltage
indicator on
No output voltage, Over Temp
indicator on, load in excess of:
2000 W: 170A (12V) or 85A (24V);
1000 W: 90 A (12V) or 45 A (24 V);
600 W: 60 A (12 V) or 30 A (24 V).
No output voltage, Over Temp
indicator on, load less than:
2000 W: 170 A (12V) or 85 A (24V);
1000 W: 90 A (12 V) or 45 A (24 V);
600 W: 60 A (12 V) or 30 A (24 V).
No output voltage, Over Load indicator
on.

8. Maintenance

Very little maintenance is required to keep your inverter operating properly. You should
clean the exterior of the unit periodically with a damp cloth to prevent accumulation of
dust and dirt. At the same time, tighten the screws on the DC input terminals.
Inverter Owner's Manual
Possible Cause
Solution
Inverter switched off.
Turn inverter ON. Check wiring to
No power to inverter
inverter.
Internal fuse open
Have qualified service technician
check and replace.
Reverse DC polarity
Have qualified service technician
check and replace fuse, OBSERVE
CORRECT POLARITY.
High input voltage
Make sure that inverter is
connected to 12 V or 24 V battery.
Check regulation of charging
system.
Poor DC wiring, poor
Use proper cable and make solid
battery condition.
connections. Use new battery.
Reduce load.
Low input voltage
Recharge battery, check
connections and cable.
Thermal shutdown
Allow inverter to cool off. Reduce
load if continuous operation
required.
Thermal shutdown
Improve ventilation, make sure
ventilation openings in inverter are
not obstructed, reduce ambient
temperature.
Short circuit or wiring
Check AC wiring for short circuit or
error.
improper polarity (hot and neutral
reversed).
Very high power
Remove or reduce load
load
15