OFF - Deactivate PQ Trigger

When not recording, select OFF for Channels A and
B PQ Config to deactivate the PQ Event Recording.
Otherwise, trigger records may fill up the available
flash memory module. See "PQ Event Storage and
Viewing" on page 53.
NOTE: The PQ function triggers on the RMS val-
ues of voltages and currents that exceed the specified
Point Limits. The RMS value must exceed the Limit
for the duration specified as Dwell.

Download Log Records

The 928A is designed to transfer AutoLogged records
(using the LOG key) to your pc. To configure Au-
tologging see "LOG Key" on pages 62ff.
To transfer records from the 928A to the pc, you
will need to have some records already stored in the
928A flash memory module. Logging is based on start
and stop times and dates. In order to use this feature
effectively make sure to set the correct time and date.
See TIME and DATE on pages 20 and 21.
1. Power on the 928A and connect the USB cable
between the 928A and the computer.
2. Start Mlink and check for a green connection
light! If red, go back to "Startup - USB Con-
nection."
3. Click the Download Log Records button.
4. If you have records to download, a Save Log As
window should appear with supplied filename.
Click the Save button, or type in another file-
name and click Save.
80