8.4 - Full deletion of the memory

When full deletion of the memory is required, to restore the default settings, perform the following procedure with the motor stationary:
01.
Press and hold buttons s and t simultaneously for 3 seconds.
02.
When all the LEDs light up simultaneously, release the buttons.
03.
LEDs L1, L2 and L3 will start flashing at the end of the procedure.
After full deletion, the limit switch recognition procedure can be restarted by running the "Quick Set-up" procedure (Paragraph 7.2).
Important - This procedure does not cancel the transmitters.

8.5 - Special functions

"Always open" function
This function is a control unit feature that enables the user to command an opening manoeuvre when the "Step-by-Step" command lasts
longer than 3 seconds. This is useful, for example, for connecting a timer contact to the "Step-by-Step" input in order to keep the gate open
during a specific time bracket.
This feature is valid regardless of the "Step-by-Step" input programming (see the "Step-by-Step Function" parameter - Table 11).
"Move anyway" function
In the event that one of the safety devices is not functioning properly or is out of order, it is still possible to command and move the gate in
"Man present" mode. For further details, refer to the "USER GUIDE" pull-out insert (final part of the manual)

8.6 - Power for external devices

To power external devices (proximity reader for transponder cards or the backlight
of a key selector) it is possible to connect the device to the product's control unit as
shown in the adjacent figure.
The power supply voltage is 24 VDC –30% to +50% with a maximum available current
of 100 mA.
9

DIAGNOSTICS

The control unit emits special signals showing the operating status or any malfunction.
The OK LED can flash red if an anomaly is detected during normal operation; in particular, it will flash several times followed by a 1-second pause
to signal the specific error/anomaly

9.1 - Warning light signals and courtesy light

Signal
Cause
2 flashes
Intervention of a photocell
1-sec pause
2 flashes
3 flashes
Intervention of the
1-sec pause
"Motor Force" limiter
3 flashes
4 flashes
Triggering of the STOP input
1-sec pause
4 flashes
5 flashes
Internal parameter memorisation
1-sec pause
error
5 flashes
6 flashes
Maximum number of manoeuvres
1-sec pause
per hour exceeded
6 flashes
7 flashes
Error in the internal electric circuits
1-sec pause
7 flashes
20 – English
Table 16 - Procedure for fully deleting the memory
Table 17 - Warning light signals and courtesy light
Solution
At the start of the manoeuvre, one or more photocells prevent movement; check
whether there are any obstacles.
This is normal when there is an obstacle hampering the closing movement.
During the movement, the gate experienced excessive friction; identify the cause.
At the start of the manoeuvre or during the movement, the STOP input intervened;
identify the cause.
Wait at least 30 seconds during which the control unit will attempt to restore the
function. If the condition persists, delete the memory and rerun the memorisation
procedure.
Wait a few minutes until the manoeuvre limiting device drops below the maximum
limit.
Disconnect all the power circuits for a few seconds and then try giving a command
again; if the condition persists it means there is a serious fault on the electronic board
or the motor cabling: perform the necessary checks and replace components, if nec-
essary.