Verify Transmitter Configuration - Emerson Rosemount 2051 Series Quick Start Manual

Pressure transmitter and flowmeters, with 4-20ma hart and 1-5vdc low power hart protocol revision 5 and 7
Hide thumbs Also See for Rosemount 2051 Series:
Table of Contents

Advertisement

Quick Start Guide
Step 5: Verify transmitter configuration
Verify the configuration using any HART capable configuration tool or Local
Operator Interface (LOI) - option code M4. Configuration instructions for a Field
Communicator and LOI are included in this step. See Rosemount 2051 reference
manual (00809-0100-4007) for configuration instructions using AMS Device
Manager.
Verifying configuration with a Field Communicator
A Rosemount 2051 DD must be installed on the Field Communicator to verify
configuration. Fast key sequences for the latest DD are shown in
For fast key sequences using legacy DD's, contact your local Emerson Process
Management representative.
Note:
Emerson recommends installing the latest DD to access the complete functionality. Visit
www.emersonprocess.com or www.hartcomm.org
1. Verify device configuration using the fast key sequences in
a. A check (
these parameters should be verified as part of configuration and startup.
b. A (7) indicates availability only in HART revision 7 mode.
12
) indicates the basic configuration parameters. At minimum,
May 2013
Table 3 on page 13
.
Table 3
.