May 2013
Perform trim with LOI (option M4)
1. Set the transmitter pressure.
2. See
Figure 13
a. Perform an analog zero trim by selecting Rerange.
b. Perform a digital zero trim by selecting Zero Trim.
Perform trim with analog zero and span (option D4)
1. Set the transmitter pressure.
2. Press and hold the zero button for two seconds to perform an analog zero
trim.
Perform trim with digital zero (option DZ)
1. Set the transmitter pressure.
2. Press and hold the zero button for two seconds to perform a digital zero trim.

Safety Instrumented Systems

For Safety Certified installations, please refer to 2051 product manual
(00809-0100-4107) for installation procedure and system requirements.

Product certifications

Approved Manufacturing Locations
Emerson Process Management - Rosemount Inc. — Chanhassen, Minnesota, USA
Emerson Process Management — Wessling, Germany
Emerson Process Management Asia Pacific Private Limited — Singapore
Emerson Process Management — Beijing, China
Emerson Process Management — Navi Mumbai, India
European Directive Information
The EC declaration of conformity can be found on page 20. The most recent
revision can be found at www.rosemount.com.
Ordinary Location Certification for Factory Mutual
As standard, the transmitter has been examined and tested to determine that the
design meets basic electrical, mechanical, and fire protection requirements by
FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
on
for the operating menu.
page 15
Quick Start Guide
17