Installing/Mounting

4.3 Application settings

Installation safety precautions
In applications with working pressures/media that can be dangerous to people,
surroundings, equipment or others in case of pipe fracture, it is recommended that special
precautions such as special placement, shielding or installation of a security guard or a
security valve are taken when the temperature sensors are mounted.
4.3
Application settings
Check of application settings
● Application and flow meter installation place
● Pulse input setting
● Pt sensor type.
● Max. flow rate.
16
WARNING
Application type and flow meter installation place can be checked via order code on
device type label.
- Calculator district heating, flow meter in return line (cold pipe) 7ME3470-xxAx-xxxx
- Calculator district heating, flow meter in forward line (warm pipe) 7ME3470-xxBx-xxxx
- Calculator chilled water, flow meter in forward line (cold pipe) 7ME3470-xxCx-xxxx
- Calculator chilled water, flow meter in return line (warm pipe) 7ME3470-xxDx-xxxx
- Calculator combined cooling/ heating, flow meter in forward line (warm pipe by heating)
7ME3470-xxEx-xxxx
- Calculator combined cooling/ heating, flow meter in return line (cold pipe by heating)
7ME3470-xxFx-xxxx
Calculator pulse input setting must fit flowmeter pulse output setting (e.g. ultrasonic
flowmeter type SITRANS FUE380). Check both type plates for settings.
Observe information of temperature sensor installation.
Max. flow rate for energy calculator must not be exceeded.
Operating Instructions, 01/2010, SFIDK.PS.022.F4.02