Applications For Interface 2; Modem With Control Signals (Standard Modem); Modem Without Control Signals - Elster EK260 Operating Manual And Installation Instructions

Volume conversion device
Table of Contents

Advertisement

Volume Conversion Device EK260

4.7 Applications for Interface 2

Depending on the application, Interface 2 must be parameterised as described here. For
each setting, pay attention to the appropriate information under Chapter 3.12, Md.S2
(page 72), particularly with regard to the EK260 power supply.

4.7.1 Modem with control signals (standard modem)

F
For connection see Chap. 5.5, page 105).
A commercially available modem is connected to the EK260.
Settings under the interface list (→ 3.12, page 71):
- Md.S2 = 2
or 7
- TypS2 = 1
- Bd.S2 = 19200
- Num.T = 2...9
or 1
- PIN
= ...

4.7.2 Modem without control signals

F
For this application the EK260 needs external power supply.
F
For connection see Chap. 5.5.2, page 106).
A modem with RS232 interface is connected to the EK260; RS232 control lines such as
"Ring", "DCD" etc. are not connected.
Settings under the interface list (→ 3.12, page 71):
- Md.S2 = 3
or 5
or 15
- TypS2 = 1
- Bd.S2 = 19200 * 19200 Bd (without using the baud rate selection)
- Num.T = 2...9
or 1
- PIN
= ...
* Normally, modems do not carry out any baud-rate selection so that with Md.S2 = "5" and
"15" the values under the addresses 02:708 (Bd.S2) and 02:709 must be the same.
For the special case of a modem with baud-rate selection the starting baud rate (e.g. 300
Bd) must be set under Bd.S2 (address 02:708) and the baud -rate identification (e.g.
19200 Bd) under the address 02:709.
The ex-works setting is: 02:708 = 19200 Bd and 02:709 = 19200 Bd.
94
if a GSM modem is not involved
if a GSM modem is involved.
RS232
19200 Bd (without using the baud rate selecti on)
if a GSM modem is not involved
if a GSM modem is involved.
This must be entered for a GSM modem with activated PIN.
Modem control through the EK260 via the data lines; no automatic
call acceptance by the modem
automatic call acceptance by the modem;
no modem control by the EK260
GSM modem automatic call acceptance;
no modem control by the EK260.
RS232
only with Md.S2 = 3 and if a GSM modem is not involved
only with Md.S2 = 3 and if a GSM modem is involved.
only with Md.S2 = 3 and if a GSM modem with activated PIN is
involved.
Elster GmbH

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

83 462 140