Table of Contents

Advertisement

3.8 System list

AD
Time
Date and time
MdTim Daylight saving: yes / no
MCyc
Measurement cycle time
OCyc
Operating cycle time
Disp
Time before display switches off
Aut.V
Time to changeover to standard display
SNo
Serial number
Ta.Rg
Ambient temperature range
Vers
Software version number
Chk
Software checksum
Time
Date and time
The date and time are displayed separately. When moving to the right within the
list structure, the date is displayed after the time. When moving to the left, only the
time is displayed.
After pressing <ENTER> for entry (set clock), the date and time are displayed
together (initially without seconds). The input mark (cursor) is located on the right -
hand display position, then after pressing
to the left so that the seconds can also be changed.
The time is updated in synchronism with the operating cycle OCyc (see below) or
after key operation.
MdTim Daylight saving: yes / no
"0" = Automatic changeover between summer and winter time OFF.
"1" = Automatic changeover between summer and winter time:
Summer time begins on the last Sunday in March at 2:00 hrs. and ends on
the last Sunday in October at 2:00 hrs.
"2" = Switchover at set times
The start and finish of daylight saving is set under the addresses 1:4A0 and
1:4A8. The times must be set each year.
MCyc Measurement cycle time
Measurements (e.g. pressure, temperature), computed values (e.g. K -value,
conversion factor) and counter readings are updated on this c ycle.
To ensure all functions, MCyc must only be set to integer factors of 60 seconds,
e.g. 5, 10, 15, 20, 30 or 60 seconds. In addition MCyc must be an integer factor of
OCyc (see below). Entries of values not satisfying these conditions are, where
possible, corrected automatically. If the EK260 does not find any suitable value
during the correction attempt, it rejects the entry with error message "6". ( → 2.3.3)
In applications subject to official calibration MCyc must be less than or equal to 20
seconds.
The standard setting is 20 seconds.
With settings less than 20 seconds the battery service life is reduced. (→ B-2 )
Elster GmbH
Designation / value
Volume Conversion Device EK260
Unit
Access Address DC
-
S
-
S
Seconds
C
Seconds
S
Minutes
S
Minutes
C
-
C
-
C
-
-
-
-
(Legends: see page 22)
again, the complete value is moved
1:400
12
1:407
7
1:1F0
8
1:1F1
8
2:1A0
8
1:1A0
8
1:180
8
3:424
8
2:190
3
2:191
4
51