Graco Reactor 2 H-30 Repair Manual page 32

Hydraulic proportioning systems
Hide thumbs Also See for Reactor 2 H-30:
Table of Contents

Advertisement

Troubleshooting
Error
Location
Error
Error
Location
Location
T4EB
Heater B
T6DA
Heater A
32
Type
Description
Type
Type
Description
Description
High Temperature
Switch B
Sensor Error A
Cause
Solution
Cause
Cause
Solution
Solution
Overtemperature
Heater was delivered too
much power, causing the
switch sensed a
fluid temperature
overtemperature switch to
open. RTD is not reading
above 230°F
(110°C).
properly. After the heater
cools down, replace RTD.
Switch closes and the error
can be cleared when the
heater temperature falls
below 190°F (87°C).
Disconnected
If heater is not actually
or loose
over temperature, check
overtemperature
all wiring and connections
switch
between the TCM and the
cable/connection.
overtemperature switches.
Overtemperature
Replace overtemperature
switch failed in the
switch.
open position.
Disconnected or
Check all wiring and
loose RTD cable or
connection to RTD.
connection.
Bad RTD.
Switch the RTD with
another and see if the error
message follows the RTD.
Replace RTD if the error
follows the RTD.
334946C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reactor 2 h-50Reactor 2 h-50 eliteReactor 2 h-xp2Reactor 2 h-xp2 eliteReactor 2 h-xp3Reactor 2 h-40 elite ... Show all

Table of Contents