Graco Reactor 2 H-30 Repair Manual page 19

Hydraulic proportioning systems
Hide thumbs Also See for Reactor 2 H-30:
Table of Contents

Advertisement

Error
Location
Error
Error
Location
Location
CACM
HCM
334946C
Type
Description
Type
Type
Description
Description
HCM Communica-
tion Error
Cause
Solution
Cause
Cause
Solution
Solution
Module does not
Insert a system token into
have software.
the ADM module and cycle
the power. Wait until the
upload is complete before
removing the token.
Dial set to wrong
Ensure the HCM dial is set
position.
to the correct position:
• H-30 = 0
• H-40 = 1
• H-50 = 2
• H-XP2 = 3
• H-XP3 = 4
No 24 VDC supply
Green light on each module
to module.
should be lit. If green light is
not lit, check to make sure
each CAN cable connection
is tight. Verify the power
supply is outputting 24
VDC. If not, check power
supply wiring. If wiring is
okay, replace the power
supply.
Loose or broken
Check the CAN cables
CAN cable.
running between GCA
modules and tighten of
needed. If the problem
still persists move each
cable around the connector
and watch the flashing
yellow light on the GCA
modules. If the yellow light
stops flashing, replace the
CAN cable.
Troubleshooting
19