Operation At Communication Error Occurrence; Operation Selection At Communication Error Occurrence (Pr.500 To Pr.502, Pr.779) - Mitsubishi Electric FR-A8ND Instruction Manual

Plug-in option devicenet communication function
Table of Contents

Advertisement

4.4

Operation at communication error occurrence

4.4.1

Operation selection at communication error occurrence (Pr.500 to Pr.502, Pr.779)

You can select operations at communication error occurrences by setting Pr.500 to Pr.502, Pr.779 under network operation.
 Waiting time for the communication line error output after a communication error
Waiting time for the communication error output after a communication line error occurrence can be set.
Pr.
500
Communication error execution waiting time
Communication line status
Communication error
Alarm signal(LF)
When a communication line error occurs and lasts longer than the time set in Pr.500, it is recognized as a communication error.
If the communication returns to normal within the time, it is not recognized as a communication error, and the operation
continues.
30
INVERTER SETTING
Name
Normal
(E.OP1)
setting time
(Pr.502 = 3)
Setting range
0 to 999.8 s
0.1 s
Normal
Error
Pr.500
Minimum setting
Initial value
increments
0 s
Error
Recognition
Pr.500
setting time
ON