3.4 Operation at Communication Error Occurrence

3.4.1

Operation selection at communication error occurrence

You can select operations at communication error occurrences by setting Pr. 500 to Pr. 502 under network
operation.
• Parameter setting
1) Pr. 500 "communication error recognition waiting time"
You can set the waiting time from when a communication line fault occurs until it is recognized as a
communication error.
Parameter Number
500
Communication line status
Communication error (E. OPT)
If the communication line fault still persists after the time set in Pr. 500 has elapsed, it is recognized as
a communication error.
When the fault is restored to normal communication within the set time, it is not regarded as a
communication error and operation continues.
Setting Range
Minimum Setting Increments
0 to 999.8s
Normal
19
0.1s
Abnormal
Recognition
Time set in Pr. 500
INVERTER SETTING
Factory Setting
0