Mitsubishi Electric FR-A8ND Instruction Manual page 47

Plug-in option devicenet communication function
Table of Contents

Advertisement

 Input Instance 70 (inverter → master)
When using Input Instance 70, set Output Instance to 20.
Byte
Bit 7
0
Reserved (0)
Reserved (0)
1
Reserved (0x00)
2
Speed actual (low byte)
3
Speed actual (high byte)
• Input Instance 70 details
Bit0
Byte0
Bit2
Byte2
Byte3
46
OBJECT MAP
Bit 6
Bit 5
Reserved (0)
Reserved (0)
Inverter error signal
Faulted
(0: inverter is under normal operation 1: inverter is in a fault state)
Forward rotation
Running Fwd
(0: other than forward rotation 1: forward rotation)
Inverter running speed (1 r/min increments)
Speed
Display range: 0 to 32767
Actual
The setting values of Pr.37, Pr.144, and Pr.811 are effective. (Refer to
Bit 4
Bit 3
Running
Reserved (0)
Fwd
Bit 2
Bit 1
Reserved (0)
Faulted
page
Bit 0
37)