 Displaying and clearing the communication error count
The cumulative count of communication error occurrences can be displayed. Write "0" to clear this cumulative count.
Pr.
501
Communication error occurrence count display
Count timing depending on
communication line status
At the point of communication line error occurrence, Pr.501 Communication error occurrence count display is incremented
by 1.
NOTE
• Communication error count is temporarily stored in the RAM memory. The error count is stored in EEPROM only once
per hour. If power reset or converter reset is performed, Pr.501 setting will be the one that is last stored to EEPROM
depending on the reset timing.
 Inverter operation at a communication error occurrence
How the inverter operates at a communication line error or an option unit fault can be set.
Pr.
502
Stop mode selection at communication error
779
Operation frequency during communication error


Valid when Pr.502 = "3".
Name
Normal
Name
0 (Initial Value), 1, 2, 3
0 to 590 Hz
9999 (Initial Value)
Minimum setting
Setting range
0
1
Error
Normal
Incremented by 1
Setting range
Refer to
When a communication error occurs, the inverter
operates at the set frequency.
The inverter operates at the frequency set before
the communication error occurs.
Initial value
increments
0
Error
Incremented by 1
Description