Mitsubishi Electric FR-A8ND Instruction Manual page 79

Plug-in option devicenet communication function
Table of Contents

Advertisement

Class 0x2A Instance 1
Attribute ID Access Data type No. of data bytes
141
Get/Set
UINT
142
Get
UINT
143
Get
UINT
144
Get
UINT
145
Get
UINT
146
Get
UINT
147
Get
UINT
148
Get
UINT
170
Get
UINT
171
Get
UINT
172
Get
UINT
174
Get
UINT
175
Get
UINT
176
Get
UINT
177
Get
UINT
178
Get
UINT
179
Get
UINT
180
Get
UINT
181
Get
UINT
182
Get
UINT
183
Get
UINT
184
Get
UINT
78
OBJECT MAP
Faults history 1 (latest)
2
Faults history all clear
2
Faults history 2 (second fault in past)
2
Faults history 3 (third fault in past)
2
Faults history 4 (fourth fault in past)
2
Faults history 5 (fifth fault in past)
2
Faults history 6 (sixth fault in past)
2
Faults history 7 (seventh fault in past)
2
Faults history 8 (eigth fault in past)
2
Output frequency (0.01 Hz)
2
Output current (0.01 A/0.1 A)
2
Output voltage (0.1 V)
2
Frequency setting value (0.01 Hz)
Running speed (1 r/min)
2
The setting values of Pr.37, Pr.144, and Pr.811 are effective. (Refer to
2
Motor torque (0.1%)
2
Converter output voltage (0.1 V)
2
Regenerative brake duty (0.1%)
2
Electronic thermal relay function load factor (0.1%)
2
Output current peak value (0.01 A/0.1 A)
2
Converter output voltage peak value (0.1 V)
2
Input power (0.01 kW/0.1 kW)
2
Output power (0.01 kW/0.1 kW)
2
Input terminal status
Definition


,







page
37)

Advertisement

Table of Contents
loading

Table of Contents