Mitsubishi Electric FR-A8ND Instruction Manual page 49

Plug-in option devicenet communication function
Table of Contents

Advertisement

 Input Instance 71 (initial value) (inverter → master)
When using Input Instance 71, set Output Instance to 21.
Byte
Bit 7
Ref From
0
AtReference
Net
1
Reserved (0x00)
2
Speed actual (low byte)
3
Speed actual (high byte)
• Input Instance 71 details
Bit0
Bit2
Running Fwd
Bit3
Running Rev
Bit4
Byte0
Bit5
CtrlFromNet
Bit6
RefFromNet
Bit7
AtReference
Byte2
Speed Actual
Byte3
48
OBJECT MAP
Bit 6
Bit 5
Ctrl From
Ready
Net
Inverter fault signal
Faulted
(0: inverter is under normal operation 1: inverter is in a fault state)
Forward rotation (0: other than forward rotation 1: forward rotation)
Reverse rotation (0: other than reverse rotation 1: reverse rotation)
Ready signal (0: operation preparation 1: operation ready)
Ready
Always "1" after power ON
0: The inverter is set not to accept the commands Bit0 and Bit1 of Byte0.
1: The inverter is set to accept the commands Bit0 and Bit1 of Byte0.
0: The inverter is set not to accept the speed commands.
1: The inverter is set to accept the speed commands.
Up-to-frequency signal (SU signal)
(Same definition with Class 0x2A Instance 1 Attribute 3. Refer to
Inverter running speed (1 r/min increments)
Display range: 0 to 32767
The setting values of Pr.37, Pr.144, and Pr.811 are effective. (Refer to
Bit 4
Bit 3
Running Rev
Running Fwd
Bit 2
Bit 1
Reserved (0)
Faulted
page
75)
page
37)
Bit 0