GE Interlogix NX-8 Installation And Startup page 39

Networx series, commercial fire panel
Hide thumbs Also See for NX-8:
Table of Contents

Advertisement

LOC
PG
45
24
OUTPUTS 1-4 PARTITION SELECTION
Segments
Partition #1
Partition #2
Partition #3
Partition #4
Partition #5
Partition #6
Partition #7
Partition #8
46
24
OUTPUTS 1-4 SPECIAL TIMING
Segments
Output timed in minutes.
Output to latch.
Output to stop timing upon user code entry.
Output to activate only between closing & opening
Output to activate only between opening & closing
Invert output (0 volts going to 12V when activated).
Reserved
Reserved
47
24
RELAY #1, EVENT & TIME
Segment #1: Program the event number for relay #1
Segment #2: Program the timing for relay #1
48
24
RELAY #2, EVENT & TIME
Segment #1: Program the event number for relay #2
Segment #2: Program the timing for relay #2
49
24
AUXILIARY OUTPUT #3, EVENT & TIME
Segment #1: Program the event number for output #3
Segment #2: Program the timing for output #3
50
25
AUXILIARY OUTPUT #4, EVENT & TIME
Segment #1: Program the event number for output #4
Segment #2: Program the timing for output #4
51
25
AUTOTEST CONTROL
Segment #1: Program a "1" if the interval is hours, a "0" if
in days. Add a A2" to suppress the daily test or a A3" to
suppress the hourly test.
Segment #2: Program the autotest interval from 1-255
days or hours.
Segment #3: Program the autotest report in 24-hour time
format.
Segment #4: Program the autotest report time (minutes
after the hour)
52
25
OPENING TIME
Segment #1: Program the hour of the opening time.
Segment #2: Program the minutes after the hour of the
opening time.
53
26
CLOSING TIME / AUTO ARMING TIME
Segment #1: Program the hour of the closing time / auto
arming time.
Segment #2: Program the minutes after hour of closing /
auto arming time.
NX-8 Commercial Fire
Technical Manuals Online! - http://www.tech-man.com
DESCRIPTION
DEFAULT
Relay1
Relay2
1
2
3
4
5
6
7
8
Relay1
Relay2
1
2
3
4
5
6
7
8
0=Burglary alarm
10 seconds
1=Fire alarm
10 seconds
2= 24 Hour Alarm
10 seconds
21-Armed State
0=Follow condition
0
24
2
0
8
0
20
0
DATA
AuxOut3
AuxOut4
1
1
1
2
2
2
3
3
3
4
4
4
5
5
5
6
6
6
7
7
7
8
8
8
AuxOut3
AuxOut4
1
1
1
2
2
2
3
3
3
4
4
4
5
5
5
6
6
6
7
7
7
8
8
8
39