LOCATION 32 - PARTITION SELECT, ZONES 25-32
(8 segments, feature selection data) Location 32 is used to select the partition(s) that zones 25-32 reside in. A zone
may reside in any combination of the 8 partitions. If a burglary zone resides in more than 1 partition it will only be
active when all partitions it resides in are armed. A zone that resides in more than 1 partition will be reported to
its lowest partition. Segment 1 corresponds to zone 25 and Segment 8 corresponds to zone 32.
Segments 1 – 8
1=
Partition #1
2=
Partition #2
3=
Partition #3
4=
Partition #4
LOCATION 33 - ZONES 33-40 ZONE TYPE
(8 segments, numerical data) Location 33 contains the Zone Type for zones 33-40. Segment 1 is for zone 33 Segment
8 is for zone 40. Default Zone Types are found in Table 9-1 on page 19. To customize a Zone Type, see page 29.
LOCATION 34 - PARTITION SELECT, ZONES 33-40
(8 segments, feature selection data) Location 34 is used to select the partition(s) that zones 33-40 reside in. A zone
may reside in any combination of the 8 partitions. If a burglary zone resides in more than 1 partition, it will only be
active when all partitions are armed. A zone that resides in more than 1 partition will be reported to its lowest
partition. Segment 1 corresponds to zone 33 and Segment 8 corresponds to zone 40.
Segments 1 – 8
1=
Partition #1
2=
Partition #2
3=
Partition #3
4=
Partition #4
LOCATION 35 - ZONES 41-48 ZONE TYPE
(8 segments, numerical data) Location 35 contains the Zone type for zones 41-48. Segment 1 is for zone 41 Segment
8 is for zone 48. Default Zone Types are found in Table 9-1 on page 19. To customize a Zone Type, see page 29.
LOCATION 36 - PARTITION SELECT, ZONES 41-48
(8 segments, feature selection data) Location 36 is used to select the partition or partitions that zones 41-48 reside in.
A zone may reside in any combination of the 8 partitions. If a burglary zone resides in more than 1 partition it will
only be active when all partitions are armed. A zone that resides in more than 1 partition will be reported to its
lowest partition. Location 36 has 8 segments. Segment 1 corresponds to zone 41 and Segment 8 corresponds to
zone 48.
Segments 1 – 8
1=
Partition #1
2=
Partition #2
3=
Partition #3
4=
Partition #4
L
LOCATION 37 - SIREN AND SYSTEM SUPERVISION
(5 segments, feature selection data) Location 37 is used to enable various system feature and reporting options.
(Refer to GLOSSARY on page 6.)
Segment 1
1 = On if siren sounds for "Telephone Line Cut" when armed.
2 = On if siren sounds for "Telephone Line Cut" when disarmed.
3 = On if siren blast at arming.
4 = On if siren blast at exit expiration.
5 = On if siren blast at closing kissoff.
6 = On if siren sounds during a
7 = On if siren sounds for a Zone or
8 = On if siren blasts 1 time for keyswitch or wireless arming; 2 times for disarming.
NX-8 Commercial Fire
Technical Manuals Online! - http://www.tech-man.com
5=
Partition #5
6=
Partition #6
7=
Partition #7
8=
Partition #8
5=
Partition #5
6=
Partition #6
7=
Partition #7
8=
Partition #8
5=
Partition #5
6=
Partition #6
7=
Partition #7
8=
Partition #8
"Cross
Zone" verification time.
Box
Tamper.
21