GE Interlogix NX-8 Installation And Startup page 10

Networx series, commercial fire panel
Hide thumbs Also See for NX-8:
Table of Contents

Advertisement

TERM
Swinger Shutdown This feature allows a zone or zones to be automatically bypassed after a
Telephone Line
Monitor
Temporal Siren
Disable
User Code
Walk-Test Mode
Wireless Sensor
Missing/Low
Battery
Zone Bypassed
Sounder Alert
Zone Types
(Configurations)
10
Technical Manuals Online! - http://www.tech-man.com
specified number of alarms. When a zone is tripped, the alarm 'counter'
reflects "1" in memory. If a new (first) alarm is detected in a different
zone, the counter remains at "1". If an alarm is detected on a previously
tripped zone, the count increments to "2". The 'counter' will increment
each time an alarm is detected on a zone with multiple trips. Bypassing
will occur on the zone that causes the count to equal the number
programmed in location 38; the 'counter' will reset to zero (0); and begin
a new trip count where the next alarm will set the 'counter' to 1. If
immediate restore is enabled in location 37, the alarms (and restores, if
enabled) will be sent as they occur. If immediate restore is not enabled,
a second or subsequent alarm will not be sent until the siren times out.
For UL installations, this feature shall be DISABLED.
The NX-8-CF has a Telephone Line Monitor that monitors the voltage
and current of the telephone line for a detection of a faulted phone line.
This condition can also be reported to the central station. If the report is
enabled, only the Telephone Line Restore will be reported unless the NX-
870E is being used.
If disabled, the Fire Siren will be steady and Fire Voltage Out will be the
same as Burglary (continuous).
temporal.
For UL installations, this must be ENABLED.
A four- or six-digit entry code used to arm or disarm the system.
If enabled, entering
CHIME followed by a user code will allow a walk-
through zone test where all zones become silent and local (non-
reporting). The number of the faulted zone(s) will be displayed on the
LCD keypad. It will also be entered into alarm memory and the internal
log. To exit at any time during this mode, enter a user code. Otherwise
the AWalk-Test Mode@ will automatically exit after 15 minutes.
The NX-8-CF will send a report to the central station when a wireless
sensor has detected a low battery or has not reported to the receiver.
The "Service Required" message will appear when either condition
exists.
If this feature is enabled, the NX-8-CF will beep the keypad sounder
upon arming if a zone is bypassed.
The NX-8-CF has 20 programmable Zone Types that determine how
each zone will function and report.
If any zone is programmed as a Fire Zone, that zone will be a Fire Zone in all
partitions. (Example: If zone 2 is a Fire Zone in partition 1, then zone 2 will be a
Fire Zone in all partitions.)
DESCRIPTION
Otherwise, the Fire Siren will be
LOC
PG
37, 38
21
37,39,40
21-22
37
21
41
23
37
21
23
18
111-149,
30-32
DEFAULT
19
ZONE TYPES