GE Interlogix NX-8 Installation And Startup page 30

Networx series, commercial fire panel
Hide thumbs Also See for NX-8:
Table of Contents

Advertisement

LOCATIONS 110 - 149 ARE USED TO CHANGE THE ZONE TYPES (Configurations) AS LISTED IN Table 9-1 ON
PAGE 19. THESE LOCATIONS ARE CONSIDERED ADVANCED PROGRAMMING AND SHOULD ONLY BE
CHANGED WITH A THOROUGH UNDERSTANDING OF THE OPERATION OF EACH BIT.
FIRE ZONE CHARACTERISTICS ARE PRESET AND CANNOT BE CHANGED IN UL LISTED SYSTEMS.
(LOCATIONS 110 –149)
LOCATION 110 - ZONE TYPE 1 ALARM EVENT CODE
(1 segment, numerical data) Location 110 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 111 - ZONE TYPE 1 CHARACTERISTIC SELECT
(3 segments, feature selection data)
Segment 1:
1 = Fire (turn on if this is a fire zone).
2 = 24 hour (turn on for non-fire 24 hour zones).
3 = Keyswitch zone. (normally open switch)
4 = Follower (turn on for burglary zones that are Instant during non-entry times).
5 = Delay 1 zone (follows timer 1 entry and exit times).
6 = Delay 2 zone (follows timer 2 entry and exit times).
7 = Interior (turn on if this zone should Automatically Bypass or Bypass for Stay Arming).
8 = Local only (turn on if this zone should not be reported).
Segment 2:
1 = On if Zone Type will beep the keypad for alarm.
2 = On if Zone Type will sound the yelping siren for alarm.
3 = On if Zone Type will sound the temporal siren for alarm.
4 = On if Zone Type will chime.
5 = On if Zone Type can be bypassed.
6 = On if Zone Type is included in the group shunt.
7 = On if Zone Type is force armable.
8 = On if Zone Type is entry guard.
Segment 3:
1 = On enables Sprinkler Supervisory
2 = On enables Double End Of Line Tamper zone. (Mainly used for tamper on wireless zones)
3 = On enables Trouble Reporting zone. (Day zone and Fire zones)
4 = On if Zone Type is a
5 = On enables Dialer Delay zone. (Location 40, page 22)
6 = On if Zone Type will swinger shutdown. (Location 38, page 22)
7 = On enables Restore reporting.
8 = Reserved
LOCATION 112 - ZONE TYPE 2 ALARM EVENT CODE
(1 segment, numerical data) Location 112 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 113 - ZONE TYPE 2 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
LOCATION 114 - ZONE TYPE 3 ALARM EVENT CODE
(1 segment, numerical data) Location 114 contains the event code sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on page 45. The zone ID will be that zone that is in alarm.
LOCATION 115 - ZONE TYPE 3 CHARACTERISTIC SELECT
(3 segments, feature selection data) Use "Zone Type Characteristic Selections" described in Location 111.
30
Technical Manuals Online! - http://www.tech-man.com
Cross
Zone.
NX-8 Commercial Fire

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for GE Interlogix NX-8

Table of Contents