GE Interlogix NX-8 Installation And Startup page 15

Networx series, commercial fire panel
Hide thumbs Also See for NX-8:
Table of Contents

Advertisement

LOCATION 4 - EVENTS REPORTED TO PHONE # 1
(2 segments, feature selection data)
Segment 1
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 =
Start and End
Segment 2
1 = Zone and
2 = Auxiliary Power Overcurrent, Ground Fault, and Restore for both.
3 = Wireless Sensor Missing and Restore.
4 = Wireless Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Reserved.
8 = Reserved.
LOCATION 5 - PARTITIONS REPORTED TO PHONE #1
(1 segment, feature selection data) Location 5 is used when events to be reported to a phone number are based upon
the partition regardless of the event. If this location is used, location 4 should be programmed as "0".
Segment 1
1=
Partition #1
2=
Partition #2
3=
Partition #3
4=
Partition #4
LOCATION 6 - PROGRAMMING PHONE #2
(20 segments, numerical data) Phone #2 is programmed in location 6. A "14" indicates the end of the phone number.
Delays of four seconds can be programmed at any point in the phone number by programming a "13" in the appropriate
segment. If tone dialing is desired, program a "15" in the segment where tone dialing should begin. If the entire number
should be tone dialing, program a "15" in the first segment. Program an A11" for a Ar@, and a A12" for a A#@.
LOCATION 7 - ACCOUNT CODE FOR THE PHONE #2
(6 segments of numerical data) The account code sent when Phone #2 is dialed is programmed in location 7. Program
a A10" in the segment immediately after the last digit of the account code. If the account code is 6 digits long, program
all 6 segments. If this location is left unprogrammed, account code 1 will be used when the second phone number is
dialed.
LOCATION 8 - COMMUNICATOR FORMAT FOR PHONE # 2
(1 segment, numerical data) Location 8 contains the communicator format used to transmit to the receiver connected to
Phone #2. Consult the instruction manual for your central station receiver to determine which format is compatible If
this location contains a "0", Phone #3 will use the same format programmed for Phone #1 in Location 2.
LOCATION 9 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE #2
(2 segments, numerical data)
Segment 1, Dial attempts
Segment 1 of Location 9 is used to enter the number of dial attempts ( 1 to 15 attempts) the communicator will
make to Phone #2 before ending the notification process. Factory default is "0" and the communicator will
make the same number of attempts as those programmed in location 3.
NX-8 Commercial Fire
Technical Manuals Online! - http://www.tech-man.com
programming.
Box Tamper
and Tamper Restore.
5=
Partition #5
6=
Partition #6
7=
Partition #7
8=
Partition #8
15

Hide quick links: