LOCATION 50- OUTPUT #4, EVENT AND TIME
(2 segments, numerical data)
Segment 1:
Use Table 9-2 on page 25 to select the event that will activate output 4.
Segment 2:
Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 4,
Location 46). Programming a "0" makes the output follow the event.
Table 9-2 AUXILIARY OUTPUT EVENT SELECTION
DATA
/
0
Burglary Alarm
/
1
Fire Alarm
/
2
24 Hour Alarm
/
3
Trouble Alarm
/
4
Tamper Alarm
5
Yelping Siren (Burglary)
6
Temporal Siren (Fire)
7
Any Siren
8
Any Bypass
9
AC Fail
10
Low Battery
/
11
Duress
/
12
Aux 1 Keypad Zone
/
13
Aux 2 Keypad Zone
/
14
Panic Keypad Zone
15
Keypad Tamper
/
16
Autotest
17
Alarm Memory
18
Entry
19
Exit
20
Entry or Exit
21
Armed State
22
Disarmed State
23
Ready
24
Not Ready
25
Fire
˜ Events 49 & 50 require NX-408, NX-416, or NX-448 wireless receivers to operate.
/ If set to follow condition, these events will be 1 second.
Notes : When Event 48 is programmed, it is possible to program a user code's authorization to select which output(s) a
particular code will activate. (Refer to "Assigning User Authority" in the NX-148ECF installation manual.)
LOCATION 51 -
AUTOTEST
(4 segments, numerical data)
Program a "1" if the interval is to be in hours; Program a "0" if in days. Add a A2" to suppress the daily
Segment 1:
test or a A3" to suppress the hourly test if any report has been sent.
Segment 2:
Program the Autotest interval from 1-255 hours/days.
Segment 3:
Program the Autotest report hour in 24-hour format (if the interval is in hours, this segment is ignored).
Segment 4:
Program the Autotest report time, number of minutes after the hour.
LOCATION 52 - OPENING TIME
(2 segments, numerical data) Location 52 contains the time in 24 hour format the NX-8-CF enables codes designated
as arm only after closing. This time is only valid on those days programmed in location 54.
Opening time must be earlier than closing time for Auto Arm, Relays, Auxiliary Outputs, or Code Authorization
to function properly.
Segment 1:
Program the hour of the opening time.
Segment 2:
Program the minutes after the hour of the opening time.
NX-8 Commercial Fire
Technical Manuals Online! - http://www.tech-man.com
EVENT
CONTROL
DATA
EVENT
26
Fire Trouble
27
Chime
/
28
Expander Trouble
29
Dynamic Battery Test Time
30
Open Period
31
Closed Period
32
Reserved
33
Line Seizure
34
Ground Start
35
Fail To Communicate
36
Telephone Line Fault
37
Program Mode
38
Reserved
39
Ground Fault
40
Short Circuit (Over-current)
41
Box Tamper
42
Siren Tamper
43
Any Open
44
Any Short
45
Any Fault (Open/ Short on Non-Fire Zone)
/
46
Any Alarm
47
Beeping Keypad
/
48
Code Entry (See note below)
49 ˜ /
Key FOB Function 1
50 ˜ /
Key FOB Function 2