GE Interlogix NX-8 Installation And Startup page 26

Networx series, commercial fire panel
Hide thumbs Also See for NX-8:
Table of Contents

Advertisement

LOCATION 53 - CLOSING TIME/AUTOMATIC ARMING TIME
(2 segments, numerical data) Location 53 contains the time in 24 hour format the NX-8-CF disables the disarm
capability for codes designated as arm only after closing. This is also the time the Automatic Arming sequence will begin
(if enabled in location 55).
Opening time must be earlier than closing time for Auto Arm, Relays, Auxiliary Outputs, or Code Authorization
to function properly.
Segment 1:
Program the hour of the closing / auto arm time.
Segment 2:
Program the minutes after the hour of the closing / auto arm time.
LOCATION 54 - DAYS OF THE WEEK EACH PARTITION IS OPEN
(8 Segments, feature selection data) Location 54 selects which days of the week each partition is open. On these
days, Aarm only after close window@ codes will be able to arm and disarm during open window.
If any partition is not programmed to be opened and is programmed to Auto-Arm (Location 55), the NX-8-CF
will try to arm every 45 minutes for the duration of the closed period.
On days not selected here, Aarm only after close window@ codes will not disarm. Segment 1 is for partition 1, and
segment 8 is for partition 8. (Locations 52 and 53 for the opening and closing times for the open days.)
Segment 1-8
1 = Open on Sunday.
2 = Open on Monday.
3 = Open on Tuesday.
4 = Open on Wednesday.
5 = Open on Thursday.
6 = Open on Friday.
7 = Open on Saturday.
8 = Reserved.
LOCATION 55 - DAYS OF THE WEEK FOR AUTO ARMING IN PARTITIONS 1 THRU 8
(8 Segments, feature selection data) Location 55 selects which days each partition will
partition 1, and segment 8 is for partition 8. If a zone is faulted when the panel tries to auto arm, the zone will be
bypassed.
Segments 1-8
1 = Auto Arming on Sunday.
2 = Auto Arming on Monday.
3 = Auto Arming on Tuesday.
4 = Auto Arming on Wednesday.
5 = Auto Arming on Thursday.
6 = Auto Arming on Friday.
7 = Auto Arming on Saturday.
8 = Reserved.
LOCATIONS 56 - 87 RESERVED.