Segment 1
Dynamic Battery Test duration in minutes 0-255 minutes ("0" = no test)
The "Dynamic Battery Test" feature cannot exceed four (4) hours. The dial delay shall be set to -0-.
Segment 2
AC Fail
Segment 3
Power Up Delay in seconds 0-60 seconds ("0" = no power up delay).
Segment 4
Siren Time in minutes 1-255 minutes.
Segment 5
Telephone Line Cut delay in seconds 10-175 seconds.
Segment 6
Cross Zone
Segment 7
Chime time in 50 mS (1/20th second) increments from 0-12 seconds ("0" = follows zone 255 latched).
Segment 8
Dial delay in seconds 0-255 seconds ("0 " = no abort delay).
Segment 9
Fire Alarm Verification time in seconds 120-240 seconds ("0" = no fire alarm verification). NOTE: This
feature is not approved for residential use in California.
Segment 10
Reserved
LOCATION 41 - SPECIAL FEATURES
(1 segment, feature selection data)
Segment 1
1 = Reserved
2 = Reserved
3 = Enable
4 = Enable
5-8 Reserved.
LOCATION 42 - GO TO PROGRAM CODE
(6 segments, numerical data) Location 42 contains the
digit code. If the 6-digit code option is enabled in Location 41, THIS CODE MUST CONTAIN SIX (6) DIGITS. If this
option is not enabled in location 41, the last 2 segments (digits) will be ignored. With the NX-8-CF disarmed, the "Go To
Program Code" can be used to enter the Program Mode.
LOCATION 43 - GO TO PROGRAM CODE PARTITION AND AUTHORIZATION
(2 segments, feature selection) The
the code to arm or disarm, the user ID is 255. (This code may not be changed in the Run Mode.)
Segment 1
1 = Reserved.
2 = On enables "Go To Program Code" as an arm only code.
3 = On enables "Go To Program Code" as an arm only after closing.
4 = On enables "Go To Program Code" as a master arm/disarm code (can change user codes)
5 = On enables "Go To Program Code" as an arm/disarm code.
6 = On enables "Go To Program Code" to bypass zones.
7 = On enables "Go To Program Code" opening and closing reports.
8 = Reserved.
NX-8 Commercial Fire
Technical Manuals Online! - http://www.tech-man.com
report delay in 0-255 hours.
time in minutes 0-255 ("0" = no cross zoning).
Auto Cancel / Abort
(Refer to GLOSSARY on page 6.)
Walk-Test Mode
(Refer to GLOSSARY on page 6.)
"Go To Program
"Go To Program
Code". This location contains either a 4 or 6-
Code" can be used as a standard arm/disarm code. When using