Controller Functions; Pid Controller - Honeywell APT4000PH User Manual

Apt4000 series, 4-wire ph analyzers
Table of Contents

Advertisement

Controller functions

PID controller

P controller
Application in integrating systems
(e.g. closed tank, batch processes).
PI controller
Application in non-integrating systems
(e.g. drains).
PID controller
The additional derivative action compensates for measurement
peaks.
Controller characteristic
+100 %
Controller output Y P
[%]
Neutral zone Y P =0
Setpoint
-100 %
82
[pH]
APT4000PH
Controller equations
Controller output Y = Y P +
P-action
Proportional action Y P
Setpoint - Meas. value
Y
=
* K
P
C
Constant
Neutral zone (Y=0)
Tolerated deviation from setpoint.
The setting "1pH", for example, permits a deviation of ± 0.5 pH
from the desired value without activating the controller.
Proportional action (Gradient K
100 %
%
K
= 500
C
50 %
X w
1 / (100)
Deviation
dY P
1
Y P dt
+ T D
T R
dt
I action
D action
with:
Y P
Proportional action
T R
Reset time [s]
T D
Rate time [s]
K C
Controller gain [%]
Constant 5 (for pH)
500 mV (for ORP)
[%])
C
%
K
= 200
C
%
K
= 100
C
%
K
= 50
C
2 / (200)
3 / (300)
4 / (400)
(Process variables: pH / (mV))
5 / (500)
83