Configuration

Controller

(for description see Pg 82 and the following)
Setpoint. Neutral zone
Menu group
Code Display
Relay / Controller
rL.
56
Select menu item
L1.
Relay 1 menu group
L2.
Relay 2 menu group
Ct.
Controller setpoint
Enter neutral zone
(P) Controller gain
(I) Reset time T
R
(D) Rate time T
D
Pulse length/Pulse frequency
PLC: Pulse length
PFC: Pulse frequency
Hold behavior
End:
Press CONF, then ENTER
APT4000PH
Code Display
Action
Ct.
Setpoint
Select with
key, proceed with ENTER
Neutral zone (dead band)
Select with
key, proceed with ENTER
Controller: P-action component
Select with
key, proceed with ENTER
Controller: I-action component (reset
time). Select with
with
Controller: D-action component
(Rate time).
Select with
key, proceed with ENTER
Pulse length/Pulse frequency
Select with
proceed with ENTER
PLC: Pulse length
Select with
key, proceed with ENTER
PFC: Pulse frequency
Select with
key, proceed with ENTER
Behavior during Hold
Select with
proceed with ENTER
Choices
07.00 pH
(
key, edit number with
XX.XX pH /
XXXX mV)
01.00 pH
(
key, edit number with
XX.XX pH /
XXXX mV)
0100 %
key, edit number with
(0010 to
9999 %)
0000 SEC
key, edit number
(0000 to
9999 SEC)
key, proceed with ENTER
0000 SEC
(0000 to
key, edit number with
9999 SEC)
PLC
(PFC)
key,
0010 sec
key, edit number with
(0001 to
0600 SEC)
0060
key, edit number with
(0001 to
0180 /min)
Y LAST
key,
(Y Off)
/min