Technical Specifications - gefran 1000 Installation And Operation Manual

Hide thumbs Also See for 1000:

Advertisement

Control outpus
Main output time
Off function
Configurable alarms
Other specifications
Type of relay contact
Logic output
Continuous output
Serial interface
Current transformer input options
Power supply (switching)
Faceplate protection
Working / Storage temperatures
Relative humidity
Environmental conditions of use
FUNCTION
Power supply cable
Relay output cables
Serial connection cable
CT connection wires
Tc input probe
"PT100" input probe
CE MARKING: The instrument conforms to the European Directives 2004/108/CE and 2006/95/CE with reference to the generic standards:
EN 61000-6-2 (immunity in industrial environment) EN 61000-6-3 (emission in residential environment) EN 61010-1 (safety).
MAINTENANCE: Repairs must be done out only by trained and specialized personnel. Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.). Use of these solvents can reduce the mechanical
reliability of the device. Use a cloth dampened in ethyl alcohol or water to clean the external plastic parts.
SERVICE: In GEFRAN è disponibile un reparto di assistenza tecnica. The warranty excludes defects caused by any use not conforming to these
instructions.
2
2 • TECHNICAL SPECIFICATIONS
Action
Main output (MAIN) with direct (hetaing), reverse (cooling) function.
On/Off, P, PD, PID control in heating and in cooling, with parameters settable with faceplate keys
Cycle time
-2...200 sec
relay, logic, continuous (0...10V / 4...20mA)
Softstart
0.0 ... 99.9 min.
Software On/Off function to deactivate the instrument.
• 3 alarm limits settable to absolute, deviation, symmetrical deviation compared to setpoint, with
reversible function (direct, reverse).
• Setting of alarm point along entire selected scale.
• Alarm (AL1) with PD output with settable parameters.
- Proportional band set on hysteresis of AL1: -199...999 (-999...1999) digit.
- Derivative time: 0,0...9,99 (0,0...19,99)min.
- Cycle time: 1...200 sec (0 per allarme On/Off).
• Alarm (AL3) can be used as load interrupt function (HB) linked to input from current transformer;
configurable current scale. 0...99,9 (0...199,9)
• Alarm selection with LBA output (open control loop).
• Settable trip time and power supplied in LBA alarm state.
• Alarm trip hysteresis (settable in range): -199...999 (-999...1999) digit.
• Manual reset (correction of control at full speed): -199...999 (-999...1999) digits.
• Offset (setting of fixed difference between actual reading of input probe and value "read" by controller):
-199...300 (-300...300) digits.
- Automatic/Manual function with bumpless at switch to automati.
With contacts 5A 250Vac at cosj = 1;
Spark suppression on NO contacts ;
24Vdc ± 10%, Rout = 470Ω (12V min. at 20mA).
Protection on polarity reverse and short circuit..
0...20mA o 4...20mA on max resistance 500Ω configurable to 0...10V with impedance of 500Ω.
Load resistance ≥ 47KΩ. (indicated in code with V and I)
Optically isolated, 4 wires. Passive Current Loop interface (1200 baud) or RS485 4 wires
Baudrate
1200 / 2400 / 4800 / 9600.
Protocol
Gefran CENCAL
T.A. 5Aac, 50/60Hz, Ri = 16mΩ
Standard: 100...240Vac/dc ± 10%
on request: 11...27Vac/dc ± 10% 50/60Hz; 9VA max.
Protected by internal fuse not serviceable by user.
IP 54
0...50°C
-20...70°C
20...85% Ur non-condensing
for internal use only, altitude up to 2000m
Installation
Panel mounting, extractable from front
Weight
320g (1000) 400g (1001, 1101)
EMC conformity has been tested with the following connections
CABLE
1 mm
2
1 mm
2
0,35 mm
2
1,5 mm
2
0,8 mm
compensated
2
1 mm
2
LENGTH USED
1 m
3,5 m
3,5 m
3,5 m
5 m
3 m
80343I_MHW_1000_07-2011_ENG