Technical Specifications - gefran GEFLEX GFX-M1 Series Operating Instructions And Warnings

Modular power controller for temperature controlled zones
Table of Contents

Advertisement

Inputs
Accuracy main input
(configurable digital filter)
Type TC (Thermocouples) (ITS90)
Cold junction error
RTD type (scale settable in indicated range,
with/without decimal point) (ITS90)
Max. line resistance for RTD
Accuracy current transformer input
Current transformer input
Accuracy voltage transformer input
Voltage transformer
Functionality
°C / °F selection
Linear scale ranges
Action - Control outputs
Max. power limit heat / cool
Cycle time - Softstart
Fault power setting
Automatic blanking
Configurable alarms
Outputs
2 continuous outputs
Power supply
Serial
Protocol for Geflex master
Optional field bus protocols
General characteristics
Working / storage temperature range
Relative humidity
SSR
Rated working voltage
Non-repetitive voltage
Switching voltage for zero
Rated frequency
Rated current AC1
Non-repetitive overcurrent (t=20ms)
I
t for blowout (t=1...10ms)
2
dv/dt critical with output deactivated
Rated isolation voltage IN/OUT
Working temperature
80331F_MHW_GFX-25/120A_05-2014_ENG
13 • TECHNICAL SPECIFICATIONS
0,2% f.s. ±1 scale points at 25°C ambient temperature
Thermal drift
0,005% f.s. / °C
Main input
TC, RTD 60mV,1V Ri≥1MΩ; 20mA Ri=50Ω
Sampling time 120 msec.
J, K, R, S, T, (IEC 584-1, CEI EN 60584-1, 60584-2)
a custom linearization can be inserted
0,1° / °C
DIN 43760 (Pt100), JPT100
20Ω
1% f.s. ± 1 scale points at 25°C ambient temperature
Internal CT 0...120A Sampling time 480msec. (1 fase), 1440msec. (3 fasi)
10% f.s. ± 1 scale points at 25°C ambient temperature on the range 0...100Vac and 400...500Vac
5% f.s. ± 1 scale point at 25°C ambient temperature on the range 100...400Vac
Internal VT 0...500Vac. Sampling time 480msec (1 fase), 1440msec (3 fasi)
Logic input
24V, 8mA
Safety
Detection of short circuit or opening of probes, LBA alarm, HB alarm
Configurable
-1999...9999
Controls
Pid, Autotune, on-off
pb - dt - it
0,0...999,9 % - 0,00...99,99 min - 0,00...99,99 min
heat / cool - on / off, PWM, GTT
0,0...100,0 %
0...200 sec - 0,0...500,0 min
-100,0...100,0 %
Maintains sampling of process variable PV; when active, disables the control
Up to 4 alarm functions assignable to an output and configurable of type: maximum, minimum,
symmetrical, absolute/relative, LBA, HB
Alarm masking
Exclusion during warm up memory, reset from digital input
2 relay outputs
NO, 3A, 250V cosj=1
2 logic outputs
24Vdc, 35mA
0/2...10V, 0/4...20mA su 500Ω max.
Power supply
24Vdc ±25%, 5W max. Remote class 2 source or limited current
Serial interface
RS485, optoisolated
Baude rate
1200, 2400, 4800, 9600, 19200
MODBUS RTU
CANopen 10K...1Mbit/sec PROFIBUS DP 9,6...12Mbit/sec
Indications
3 LEDs (diagnostics) + lamp (presence of high voltage)
Protection
IP20
0...40°C / -20...70°C; Maximum surrounding air temperature 40°C
20...85% Ur not condensing
Barra DIN EN50022 or pannel from 5MA screws
Installation
25A
Weight max
650gr
850gr
Nominal voltage
480Vac
24...253Vac
1200Vp
≤ 20V
50...60Hz
25A
40A
≤ 400A
≤ 600A
≤ 645A
s
≤ 1010A
2
1000V/ms
4000V
see dissipation curves
40A
60A
75A
1300gr
1500gr
60A
75A
≤ 1150A
≤ 1500A
s
≤ 6600A
s
≤ 8000A
2
2
90A
120A
1500gr
1600gr
90A/120A
≤ 1500A
s ≤ 11200A
s
2
2
19