Standard protection level 19. Phase CFG2 parameters are
not subject to software protection (access to phase CFG2
depends only on state of jumper S9 (HW config.).
_AI/: Alarm output function.
Configuration of symmetrical deviation alarms requires setting
of positive setpoints only. For correct function, negative values
are not allowed (even if settable).
0 = Alarms 1 and 2 direct absolute (relay energized when
alarm limit is exceeded).
1 = Alarm 1 deviation, Alarm 2 absolute, both direct.
2 = Alarm 1 absolute, Alarm 2 deviation, both direct.
3 = Alarm 1, Alarm 2 direct deviation.
4 = Alarm 1 reverse absolute
(relay energized below alarm limit),
Alarm 2 direct absolute.
5 = Alarm 1 reverse deviation, Alarm 2 direct absolute.
6 = Alarm 1 reverse absolute, Alarm 2 direct deviation.
7 = Alarm 1 reverse deviation, Alarm 2 direct deviation.
8 = Alarm 1 direct absolute, Alarm 2 reverse absolute.
9 = Alarm 1 direct deviation, Alarm 2 reverse absolute
10 = Alarm 1 direct absolute, Alarm 2 reverse deviation.
11 = Alarm 1 direct deviation, Alarm 2 reverse deviation.
12 = Alarm 1, Alarm 2 reverse absolute.
13 = Alarm 1 reverse deviation, Alarm 2 reverse absolute.
14 = Alarm 1 reverse absolute, Alarm 2 reverse deviation.
15 = Alarm 1, Alarm 2 reverse deviation.
By adding 16 to the selected function code (ex. 9+16 setting
25), AL1 becomes symmetrical deviation: in this case, a direct
alarm corresponds to an alarm with relay energized outside the
"window", while a reverse alarm corresponds to an alarm with
relay energized inside.
By adding 32, AL2 becomes symmetrical deviation.
By adding 48, both alarms become symmetrical deviation.
Out/: Main output function (Heat/Cool) and AL1 (PD) enable
HB alarm and selection of temperature scale (°C or °F)
Set code for selected combination of functions as per the table.
Nr.
Al.HB
0
Disabled
1
Enabled
2
Disabled
3
Enabled
4
Disabled
5
Enabled
6
Disabled
7
Enabled
8
Disabled
9
Enabled
10
Disabled
11
Enabled
12
Disabled
13
Enabled
14
Disabled
15
Enabled
By adding the following 6 STEPS to the 16 combinations, you
can get various combinations for AL3.
+0
AL3 NORMAL DIRECT ABSOLUTE
+16
AL3 DEVIATION DIRECT NORMAL
+32
AL3 ABSOLUTE REVERSE NORMAL
+48
AL3 DEVIATION REVERSE NORMAL
+80
AL3 DEVIATION DIRECT WINDOW
+112 AL3 DEVIATION REVERSE WINDOW*
When limit AL3 = 0 or is negative, AL3 remains energized or
de-energized at all times.
Note:The PD alarm cannot be symmetrical.
80343I_MHW_1000_07-2011_ENG
7 • PROGRAMMING
AL1
OUT
Scale
NO PD
HEAT
°C
NO PD
HEAT
°C
PD
HEAT
°C
PD
HEAT
°C
NO PD
COOL
°C
NO PD
COOL
°C
PD
COOL
°C
PD
COOL
°C
NO PD
HEAT
°F
NO PD
HEAT
°F
PD
HEAT
°F
PD
HEAT
°F
NO PD
COOL
°F
NO PD
COOL
°F
PD
COOL
°F
PD
COOL
°F
TyP/ Type of input probe or linear scale.
Code
1000
0
J 0...800°C/32...999°F
1
K 0...999°C/32...999°F
2
N 0...999°C/32...999°F
3
S 0...999°C/32...999°F
4
R 0...999°C/32...999°F
5
T -100...400°C
-148...752°F
6
PT100 -199...400°C
-199...752°F
7
PT100 -19,9...99,9°C
-19,9...99,9°F
8
0-50mV no decimals (xxx)
-999...1999
9
0-50mV 1 decimals (xx.x)
10
0-50mV 2 decimali (x.xx)
11
PT100 -19,9...99,9°C
-3,8...99,9°F
12
10-50mV no decimals (xxx)
13
10-50mV 1 decimals (xx.x)
14
10-50mV 2 decimals (x.xx)
For TC probes type S and R, precision is in the instrument
class (0.5%) for temperatures > 200°C
Ct.A / AL1 Cycle time in range 0...200 sec.
dt.A / AL1 Derivative time in range 0.00...9.99 min. (1000)
0.00...19.99 min (1001-1101).
oFt / Input offset adjustment
for 1001/1101:
-300/300
for type 0,1,2,3,4,5,6,8
-30.0/30.0
for type 7,9
-3.00/3.00
for type 10
for 1000:
-199/300
for type 0,1,2,3,4,5,6,8
-19.9/30.0
for type 7,9,
-1.99/3.00
for type 10
LO.S / Minimum value of setpoint and absolute alarms in scale
range of selected probe. Start of linear scale for probe type 8,
9, 10, 12, 13, 14
Hl.S / Maximum value of setpoint and absolute alarms in scale
range of selected probe. End of linear scale for probe type
8,9,10, 12, 13, 14.
rEL/ Setting of alarm output state in case of broken probe
(message Sbr/Err on display), according to table:
rEL
Output AL1
0
ON
1
ON
2
OFF
3
OFF
4
ON
5
ON
6
OFF
7
OFF
Note: In case of broken probe, each relay assumes the set
state (ON = energized, OFF = de-energized), which does not
depend on the type of alarm (direct or reverse).
1001/1101
J 0...800°C/32...1472°F
K 0...1300°C/32...1999°F
N 0...1300°C/32...1999°F
S 0...1600°C/32...1999°F
R 0...1600°C/32...1999°F
T -100...400°C
-148...752°F
PT100 -200...400°C
-328...752°F
PT100 -199,9..199,9°C
-199,9..199,9°F
0-50mV no decimals (xxxx)
0-50mV 1 decimals (xxx.x)
0-50mV 2 decimals (xx.xx)
PT100 -19,9...199,9°C
-3,8...199,9°F
10-50mV no decimals (xxxx)
10-50mV 1 decimals (xxx.x)
10-50mV 2 decimals (xx.xx)
Output AL2
Output AL3
ON
ON
ON
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
7