1200/1300
CONTROLLER
cod. 80309 - 01/2014 - ENG
iNstallatioN aND opERatioN maNual
Side 1
1 Dimensions and cut-out; panel mounting
2 Installation and connection
3 Description of faceplate
4 Connections
Side 2
5 Technical specifications
6 "Easy" programming and configuration
7 Quick start guide
the complete manual is available for download from the
website www.gefran.com
GEFRAN spa reserves the right to make any aesthetic or
functional change at any time and without notice.
iD
symbol
Function
PV : Shows the process variable, the menu identification, the parameters identification and the error codes
SV : Shows the setpoint value, the value of the parameter displayed in PV and three dashes (- - -) when PV contains a menu
heading
Increases/Decreases the value of the parameter displayed in SV until the max/min. value is reached.
Held down: progressively increases the speed of increasing/decreasing the value displayed in SV.
Used to move between the various menus and parameters of the controller.
Confirms the value of the current parameter (or parameter edited using
Button with configurable function: with standard configuration commutes the
controller operating mode (MANUAL/AUTOMATIC).
Is only on when the display
shows the process variable.
(for configuration see parameter BVT in the KRD menu) )
+
Confirms the value of the current parameter (or parameter edited using
Output status indicators:
OUT1 (AL1), OUT2 (Main), OUT3 (HB), OUT4
1200
Outputs
Out3 - Out4
Digital inputs /
CT Input
Serial line
Always make the connections using cable types suitable for
the voltage and current limits given in Section 5 - Technical
Specifications.
If the Controller has faston terminals these must be protected and
isolated.
If it has screw terminals, the wires must be attached, at least in pairs
power supply
~
Standard:
100...240Vac/dc ±10% , max 18VA
PWR
~
Optional:
11...27Vac/dc ±10%, max 11VA 50/60 Hz
inputs
linear input with 3-wire transmitter
tc input
supplied from the instrument
+
Available thermocouples:
J, K, R, S, T
Connect for
(B,E, N, L, U, G, D, C
possible by inserting a
0/4..20mA
custom linearization)
- Observe polarities
input
- For extensions, use the
correct compensating cable
for the type of TC used
linear input with 2-wire
linear input (i)
transmitter supplied from the
instrument
+
VT
24V
+
+
4..20mA
Jumper S3 closed on
Linear input in
CPU board (see CAP.
Direct Current
6 Maintenance)
0/4..20mA, Ri = 50W
1 • DimENsioNs aND cut-out; paNEl mouNtiNG
1200
a
For correct and safe installation, follow the instructions and observe the warnings contained in this manual.
To fix the unit, insert the brackets provided into the seats on either side of the case.
To mount two or more units side by side, respect the cut-out dimensions shown in the drawing.
3 • DEscRiptioN oF FacEplatE
) and selects the next parameter.
) and selects the previous parameter.
4 • coNNEctioNs
inputs
linear input (V)
PWR
Linear input in
Direct Current
60 mV, 1V (Ri > 1MW)
5V, 10V (Ri > 10KW)
Outputs
+
Out1 - Out2
outputs out1, out 2
out 1
Inputs
- Relay 5A
NC
250Vac/30Vdc
C
NO
NC not
available if
Out2 is triac
type
outputs out3, out 4
out 3
- Relay 5A 250Vac/30Vdc
- Logic 24V 10V a 20mA
- Direct 0...10V, 0/4...20mA
- Analogue 0...10V, 0/4...20mA
Out3
- 0/2...10V (S1-ON),
+
0/4...20mA (S1-OFF)
S1 is a jumper on the board
for continuous or analogic
output
Digital inputs / ct input
iN1, iN2 digital inputs
+
VT
24V
+
Digital input 24V 5mA
S
(Jumpers S1, S2 in position P)
COM
+
or from non-powered terminal
IN2
(Jumpers S1, S2 in position N)
IN1
Hrd Menù configuration
Parameter diG or di2 = +16
serial line
modbus 2 wires (standard)
GND
+
B
(data -)
A
(data +)
a
(a)
panel fixing brackets
Panel mounting:
Function indicators: with standard configuration they show
the controller operating status.
For configuration see parameter LD. 1 , LD. 2 , LD. 3 in the KRD
L1 MAN/AUTO =
L2 SETPOINT 1/2 = OFF (IN1= OFF local Setpoint 1)
L3 SELFTUNING = ON (Self activated)
ptc/Ntc/pt100/Jpt100 input
T
2-wire connection
3-wire connection
User configurable generic outputs
out 2
out 2
- Relay 5A
250Vac/30Vdc
- Logic 24V
-
(10V a 20mA)
C
+
NO
User configurable generic outputs
out 4
- Relay 5A 250Vac/30Vdc
- Logic 24V (10V a 20mA )
Out4
+
S1
User configurable generic inputs
ct, iN1 inputs
COM
TA
IN1
N
S1
P
N
S2
modbus 4 wires / cencal
RS485 isolated serial line
+
Rx
+
Tx
s1
2 • INSTALLATION & CONNECTION
This section contains the instructions necessary for
1300
correct installation of the 1200/1300 controllers into the
machine control panel or the host system and for correct
connection of the controller power supply, inputs, outputs
and interfaces.
Before proceeding with installation read the
following warnings carefully!
Remember that lack of observation of these warnings
could lead to problems of electrical safety and
electromagnetic compatibility, as well as invalidating
the warranty.
Electrical power supply
• the controller is NOT equipped with an On/Off switch: the user
must provide a two-phase disconnecting switch that conforms
to the required safety standard (CE marking), to cut off the
power supply upstream of the controller.
The switch must be located in the immediate vicinity of the
controller and must be within easy reach of the operator. One
switch may control more than one controller.
• if the controller is connected to NOT isolated electrical
equipment (e.g. thermocouples), the earth connection must be
made with a specific conductor to prevent the connection itself
from coming directly through the machine structure.
• if the controller is used in applications with risk of damage to
persons, machinery or materials, it is essential to connect it up
to auxiliary alarm equipment. It is advisable to make sure that
alarm signals are also triggered during normal operation.
The controller must NOT be installed in flammable or explosive
environments; it may be connected to equipment operating
in such atmospheres only by means of appropriate and
adequate types of interface, conforming to the applicable safety
standards.
Notes concerning Electrical safety and
Electromagnetic compatibility:
cE maRKiNG:
OFF (automatic control)
The instrument conforms to the European Directives 2004/108/
ON (manual control)
CE and 2006/95/CE with reference to the generic standards:
EN 61000-6-2 (immunity in industrial environment) EN 61000-6-3
(emission in residential environment) EN 61010-1 (safety).
ON (IN1=ON local Setpoint 2)
Series 1200/1300 temperature controllers are mainly designed to
operate in industrial environments, installed on the switchboards
or control panels of productive process machines or plants.
OFF(Self deactivated)
advice for correct installation for Emc
instrument power supply
• The power supply to the electronic equipment on the
switchboards must always come directly from an isolation
device with a fuse for the instrument part.
• The electronic instruments and electromechanical power
devices such as relays, contactors, solenoid valves, etc., must
always be powered by separate lines.
• When the electronic instrument power supply is strongly
disturbed by the commutation of transistor or power units
or motors, an isolation transformer should be used for the
controllers only, earthing the screen.
• It is essential that the plant has a good earth connection:
- the voltage between neutral and earth must not be >1V
- the Ohmic resistance must be <6W;
• If the mains voltage fluctuates strongly, use a voltage stabilizer.
• In the proximity of high frequency generators or arc welders,
use adequate mains filters.
Jumper S2 closed
• The power supply lines must be separate from the instrument
on CPU board
input and output ones.
(see CAP. 6
Maintenance)
inputs and outputs connection
T
Use wires of
adeguate diameter
• The externally connected circuits must be doubly isolated.
(min. 1mm
)
2
• To connect the analogue inputs (TC, RTD) the following is
necessary:
- physically separate the input cables from those of the power
supply, the outputs and the power connections.
- use woven and screened cables, with the screen earthed in
one point only
• To connect the regulating and alarm outputs (contactors,
solenoid valves, motors, fans, etc.), fit RC groups (resistance
Triac
and condensers in series) in parallel to the inductive loads that
20...240Vac,
operate in Alternating Current.
max. 1A ± 10%
(Note: all the condensers must conform to VDE (class X2)
standards and withstand a voltage of at least 220V AC. The
~
resistances must be at least 2W).
~
• Fit a 1N4007 diode in parallel with the coil of this can be
load
removed inductive loads that operate in Direct Current.
GEFRaN s.p.a. declines all responsibility for any
damage to persons or property caused by tampering,
neglect, improper use or any use which does not
conform to the characteristics of the controller and to
the indica tions given in these instructions for use.
Warnings and instructions for mounting to the panel
instructions for installation category ii, pollution
level 2, double isolation.
• only for low power supply: supply from Class 2 or low voltage
limited energy source.
• the power supply lines must be separate from the controller
input and output ones
• group the instruments together keeping them separate from the
powered part of the relay
• do not install high-power remote switches, contactors, relays,
thyristor power units (especially the "phase angle" type),
motors, etc. in the same switchboard
- Input from current transformer
• avoid dust, humidity, corrosive gasses and heat sources
50mAac, 10W 50/60Hz
• do not block the ventilation holes: the working temperature
must be between 0...50°C
- Digital input 24V 5mA
• surrounding air: 50°C
(Jumpers S1, S2 in position P)
• use 60/75°C copper (Cu) conductor only, wire size range 2x No
or from non-powered terminal
22 - 14AWG, Solid/Stranded
(Jumpers S1, S2 in position N)
• use terminal tightening torque 0.5N m
Hrd Menù configuration
Nominal ambient conditions
Parameter diG or di2 = +16
Altitude
S1
P
S2
Working/storage
temperature
Non condensing
relative humidity
Before supplying the controller with power, make
RS485 isolated serial line
sure that the mains voltage is the same as that
shown in the last number of the order code.
For configuration
Modbus 4 wires/Cencal.
s1
Up to 2000m
0..50°C/-20...70°C
20...85%