11. External input and output
11-1. Compact cassette, slim duct, wall mounted, floor/ceiling,
and floor types
External input
Indoor unit
type
Control input
Compact
cassette
Slim duct
Wall mounted
Floor/Ceiling
Floor
¢ External input
With using external input function, some functions on this product can be controlled from an exter-
nal device.
• "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor
unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
Control input (Operation/Stop or Forced stop)
Wall mounted
The air conditioner can be remotely operated by means of the following on-site work.
Operation is started at the following contents by adding the contact input of a commercial on/off
switch to a connector on the external control PCB and turning it on.
Unit operation
Operation mode
Set temperature
Airflow mode
Air direction (swing)
Operation
status output
●
●
●
●
●
●
●
●
●
●
Indoor unit type
Compact cassette
Slim duct
LU/LM
Floor/Ceiling
Floor
Initial setting after power is on
Auto changeover
24 °C
AUTO
Standard air direction (swing: off)
- 138 -
External output
Fresh air
Auxiliary
control output
heater output
●
●
―
―
―
LF
Starting mode other than initial
Mode at previous operation
Temperature at previous operation
Mode at previous operation
Air direction at previous operation
Error status
output
―
―
●
―
●
―
(LU/LM types)
―
―
―
―
Connector
CN102
CNA01
CN14
CN102
CN14
setting