Work method when reinforcing the heat insulation of on-site piping
Slit of heat insulating material
facing upward
Covered gas
pipe (heat
insulation
strengthened)
Heat insulating material
(procured at the site)
Condition
When using an
When using an external duct to take in new fresh air,
external duct.
etc., condensation may form on the surface of the duct
due to the effect of the outside air temperature and the
humidity inside the ceiling.
When the
If the cold or warm air blown out from the air conditioner
remote
directly contacts the thermostat section of the remote
controller
controller, the outlet temperature of the air conditioner
installation site
may be sensed and room temperature control will be
is bad.
different from the room temperature, and "not cooled" or
"not heated" or other trouble may occur.
In addition, there is the possibility that the same kind of
trouble may also occur when the remote controller is
effected by direct sunlight.
When
When the wall mounted type was installed in a bedroom,
installation
living room, or other quiet place, the sound of the
environment is
refrigerant flow may be sensed as noise and must be
quiet.
taken into account.
When installing
In the case of the ceiling chamber system (duct is not
duct type in
installed at indoor unit inlet side and room air is sucked
ceiling
into the indoor unit through the inside of the ceiling), the
chamber
thermistor inside the indoor unit may not correctly detect
system.
the room temperature.
• Heating operation: Room is not heated because the
indoor unit is easily turned off by the thermostat.
• Cooling operation: Room is too cold because the
indoor unit is difficult to turn off by the thermostat.
When the
Cooling operation does not cool the room and heating
outlet air is
operation does not heat the room because the short
sucked in at
circuited indoor unit is not turned on by the thermostat.
duct type.
When using the
Signals may not be received when using it in a room
wireless
illuminated by an inverter fluorescent lamp.
remote
controller.
When installing
It may generate noise in TV sets, stereos and PCs.
the inverter
type.
Heat insulation reinforcement material
Flare connection
(procured at the site)
Small exposed part
Binding material
of copper pipe is desirable.
Fig. B
Contents
- 272 -
To indoor unit
Fit tightly
(purpose is to cover the sealant)
Countermeasures (Reference)
Always perform heat insulation
processing.
(Heat insulating material: Glass
wool 25-mm [1-in] thick or more.)
1. Install the remote controller
where it will not be directly
exposed to the cold or hot air.
2. Install the remote controller
where it will not be directly
exposed to sunlight or strong
lighting.
1. Plan installation of a model
with external expansion valve.
2. Plan installation of a branch
box farther from indoor unit.
3. Plan installation using another
air conditioner.
Replace the indoor unit thermistor
with optional Remote sensor unit,
and install the sensor where the
room temperature can be correctly
detected.
1. Reconsider the ventilation port
construction.
2. Replace the indoor unit
thermistor with optional
Remote sensor unit, and install
the sensor where the room
temperature can be correctly
detected.
Turn on the fluorescent lamp and
check if the indoor unit receives the
signals from the remote controller.
If the indoor unit does not receive
the signals, consult an authorized
service personnel.
The inverter type should be
installed at a sufficient distance
from these equipments.