Model name
Power supply
Available voltage range
Capacity
Input power
Running current
Cooling
Airflow rate
Fan
Heating
Type × Q'ty
Motor output
Cooling
Sound pressure level *
Heating
Cooling
Sound power level
Heating
Dimensions (H × W × D)
Fin pitch
Heat exchanger type
Rows × Stages
Pipe type
Fin type
Net
Dimensions
(H × W × D)
Gross
Net
Weight
Gross
Liquid
Size
Connection
Gas
pipe
Method
Cooling
Operation range
Heating
Material
Drain hose
Size
Model name
Material
Color
Cassette grille
Dimensions
(H × W × D)
Weight
Remote controller type
NOTES:
• The protective function might work when using it outside the operation range.
• *: Sound pressure level:
– These are the measured values in the manufacturer's anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
kW class
W
A
HIGH
MED
LOW
QUIET
3
m
/h
HIGH
MED
LOW
QUIET
W
HIGH
MED
LOW
QUIET
dB (A)
HIGH
MED
LOW
QUIET
dB (A)
mm
mm
mm
kg
mm (in)
°C
%RH
°C
mm
Net
mm
Gross
Net
kg
Gross
- 10 -
AUYG14LVLB
1Ø 230 V ~50 Hz
198—264 V
4.0
28
0.22
680
580
490
410
700
620
550
430
Turbo fan × 1
54
40
35
32
29
40
37
34
29
52
52
210 × 1,310 × 13.3 + 210 × 1,250 × 13.3
1.2
2 × 10
Copper tube
Aluminum
245 × 570 × 570
265 × 730 × 625
15
18
Ø6.35 (Ø1/4)
Ø12.70 (Ø1/2)
Flare
18 to 32
80 or less
16 to 30
Hard PVC
Ø 25 (I.D.), Ø 32 (O.D.)
UTG-UFYD-W
PS
White
(Approximate color of Munsell N 9.25/)
49 × 700 × 700
120 × 765 × 755
2.6
4.5
Wireless (Wired [option])
AUYG18LVLB
5.0
39
0.30
750
610
520
410
800
710
600
450
42
37
33
29
44
40
37
30
54
56