Slc Loop Shield Wiring - Notifier AM-6000 Installation Manual

Analog fire alarm control panel
Table of Contents

Advertisement

FOR SLC LOOP WHICH IS NOT CONTAINED IN PIPING OR METAL PIPING
A)
NOTE
:
maintain the continuity of the shield wire throughout the loop, BUT DO NOT connect to any devices.
Connect the shield wire to the outside of the control panel cabinet and the cabinet to Earth.
FOR SLC LOOP WHICH IS CONTAINED IN METAL PIPING OR IN CONDUIT
B)
:
NOTE
in this case, DO NOT allow the shield drain or shield foil to touch the cabinet.
For Style 6 field wirings, connect ONLY ONE END of the shield to the negative side of Channel A.
Maintain the continuity of the shield wire throughout the loop, BUT DO NOT connect to any devices.
Page 21
NOTIFIER ITALIA

SLC LOOP SHIELD WIRING

CABINET
CABINET
Installation Manual
( + )
( - )
Rev. B.1
( + )
( - )
AM-6000-60001.VP
Doc. M-180.2-AM6000-ENG