Notifier AM-6000 Installation Manual page 30

Analog fire alarm control panel
Table of Contents

Advertisement

• Power sup ply troub le.
Any power sup ply troub le ge ne ra te a sy stem troub le and a ge ne ral troub le si gnal; the ge ne ral troub le re lay is
de- ac ti va ted and the buz zer so und.
• Mains troub le.
It an nun cia tes that the mains vol ta ge is less than 50 Vac.
In case of troub le for mains loss, the fol lowing items are ac ti va ted: sy stem troub le led, ge ne ral troub le led,
buz zer and the mains loss troub le mes sa ge is shown on the LCD di splay.
• In suf fi cent ten sion on the main power sup ply.
The mains vol ta ge is ve ri fied to be less than 170 Vac.
If a mains troub le has been si gnal led (vol ta ge <= 50 VDC), this troub le si gnal will not be di splayed.
• In suf fi cent ten sion on the au xi lia ry power sup ply.
It in di ca tes that the mains vol ta ge is less than 170 Vac.
If the re has been a mains troub le (vol ta ge <= 50 VDC), this troub le si gnal will not be di splayed.
• In suf fi cent ten sion on the bat te ry char ger.
It in di ca tes that the mains vol ta ge is less than 170 Vac.
If the re has been a mains troub le (vol ta ge <= 50 VDC), this troub le si gnal will not be di splayed.
• Over vol ta ge on the main power sup ply.
It in di ca tes that the mains vol ta ge is more than 263 Vac.
• Over vol ta ge on the au xi lia ry power sup ply.
It in di ca tes that the mains vol ta ge is more than 263 Vac.
• Over vol ta ge on the bat te ry char ger .
It in di ca tes that the mains vol ta ge is more than 263 Vac.
• Main power sup ply fai lu re or over load.
It in di ca tes that the main power sup ply out put vol ta ge is less than 21 Vdc.
• Au xi lia ry power sup ply fai lu re or over load.
It in di ca tes that the au xi lia ry power sup ply out put vol ta ge is less than 21 Vdc.
• Main power sup ply user fuse.
This troub le si gnal in di ca tes the fol lowing con di tion:
out put user vol ta ge < 17 Vdc
• Di scon nected au xi lia ry power sup ply si gnal.
Each troub le on the au xi lia ry power sup ply is si gnal led only if its con nec tion has been set ted in the sy stem
pro gram ming.
The con nec tion of the au xi lia ry power sup ply board is ve ri fied by a < 4 Vdc vol ta ge si gnal.
• Au xi lia ry power sup ply user fuse troub le.
This troub le si gnal in di ca tes the fol lowing con di tion:
• Si ren out put fuse troub le.
This troub le si gnal in di ca tes the fol lowing con di tion:
Out put si ren vol ta ge < 17 Vdc
• Scat ter on earth troub le.
This troub le si gnal in di ca tes that the re is a scat ter on earth (po si ti ve or ne ga ti ve) with an in te gra tion of 30 sec..
The re is a jum per to enab le or di sab le this si gnal.
Bat te ry Char ger Sec tion
Appendix.VP
Doc. M- 180.2- AM6000-ENG
out put user vol ta ge < 17 Vdc
In stal la tion Manual
Rev. B.2
Page 28