The AM6000 control panel requires connection to a separate 220 VAC 50 Hz line, which must be labeled "FIRE
ALARM".
No other equipment may be powered from the circuit employed for the fire alarm system.
Overcurrent protection for this circuit must comply with local normatives.
Use proper section wire with minimum 600-volt insulation.
TABLE 1 : 220 VAC service line current requirements
The table 1 allows to calculate the total amount of current, in AC amps, that the AC service line must be capable
of supplying to the system.
Device
Type
Main Power Supply
AVPS-6
Page 23
NOTIFIER ITALIA

THE 220 VAC POWER SUPPLY LINE

Number of
Multiply
Devices
by
1
x
(
) max 1
x
Installation Manual
Current in
Amps (each)
0,9
0,45
Total amount of current required
for 220 VAC circuit
Rev. B.1
Total Current/
Type
0,9
Amps
AM-6000-60003.VP