CABLE REQUIREMENTS
Type of cable: 2-conductor TWISTED-SHIELDED cable.
Sections concerning the line total lenght (for the line “STYLE 6", the operator must consider the loop lenght) which
CANNOT exceed 3000 meters and whose resistance must be lower than 40 Ohm.
Example:
Up to
500 mt. - cable 2 x 0.5 mm
Up to 1.000 mt. - cable 2 x 1 mm
Up to 1.500 mt. - cable 2 x 1.5 mm
Up to 2.000 mt. - cable 2 x 2 mm
Up to 2.500 mt. - cable 2 x 2.5 mm
Up to 3.000 mt. - cable 2 x 3 mm
As far as the laying of cables is concerned, follow the below listed instructions:
- Suitable pipes;
- The cables must run at a proper distance from the power lines and must not be in the vicinity of any High Voltage.
Troubles often may be caused by:
Air-conditioning installation
Engines or electric welding machines
Electrical furnaces and elevators
Radio links, etc.
ELECTRIC POWER
Power Supply Voltage: 220 V single phase +/- 10%.
Frequency: 50 Hz +/- 1 Hz.
»
: pay special attention when installing the system near big electromagnetic sources (REPEATERS).
NOTE
EARTH PLANT
The earth plant must be performed according to the CEI and ISPLES rules. The resistance CANNOT exceed
10 Ohm (to be measured at the well with disconnected mains).
AM-6000-60001.VP
Doc. M-180.2-AM6000-ENG
Installation Manual
Rev. B.1
Page 20