Notifier AM-6000 Installation Manual page 29

Analog fire alarm control panel
Table of Contents

Advertisement

In put and Out put
• Mains in put
In put vol ta ge 230 Vac with 5A pro tec tion fuse
• Mains Tran sfor mer
N° 2 39 Vac 3A au xi lia ri es
The first au xi lia ry powers the rec ti fi ca tion cir cuit of the main power sup ply with a 4A pro tec tion fuse.
The se cond au xi lia ry powers the rec ti fi ca tion cir cuit of the au xi lia ry power sup ply with a 4A pro tec tion fuse.
The tran sfor mer to tal power is 200 VA
• + 24V User Out put
Out put vol ta ge 27,6 V 2A . 3A pro tec tion fuse.
• + 24V Re set tab le user Out put
Re set tab le out put ta ken from the +24V User by 5A/ 30 VDC re lay con tacts.
• + 24V Au xi lia ry Out put (on AVPS- 600)
Out put vol ta ge 27,6 V 3A . 3A pro tec tion fuse
• + 24V Re set tab le Au xi lia ry Out put (on AVPS- 600)
Re set tab le au xi lia ry out put ta ken from the +24 V au xi lia ry by 5A/ 30 VDC re lay con tacts.
Vi sual in di ca tions on the P.S.U. board
Gre en LED = "Pa nel powe red (mains 220 VAC or Bat te ri es)" - in di ca tion
Yel low LED = "Bat te ry low" - troub le
Gre en LED = "Bat te ry char ger ok" - in di ca tion
Yel low LED = "Po si ti ve scat ter on earth" - troub le
Yel low LED = "Ne ga ti ve scat ter on earth" - troub le
Gre en LED = "Main P .S.U. ok" - in di ca tion
Gre en LED = "A.V.P .S. ok" - in di ca tion
Trou bles In di ca tion List
Page 27
NO TI FIER ITA LIA
AP PEN DIX: AM- 6000 POWER SUP PLY
BLOCK DIAGRAM
In stal la tion Manual
Rev. B.2
Appendix.VP
Doc. M- 180.2- AM6000- ENG