11 Supplement
11.1 Technical data
General data
Series
Dimensions
Weights
Housing materials
Socket materials
Screwed terminals
Voltage supply
Operating voltage
Power consumption
Sensor input
Number of sensors
Kind of input (selectable)
- Active input
- Passive input
Measured value transmission
- HART protocol (Multidrop)
Terminal voltage
- non-Ex version
- Ex version
Current limitation
Adjustment range HART sensor
- Adjustment range
- min. adjustment delta
Connection cable
Fail safe relay
Contact
VEGASCAN 693 - 15-channel HART signal conditioning instrument
1)
Selection is made via the terminals, a mixed operation active/passive is not
1)
possible.
module unit with plug-in socket for mounting on
carrier rail 35x7.5 acc. to EN 50022
W = 72 mm (2.83 in), H = 118.5 mm (4.66 in), D
= 134 mm (5.28 in)
approx. 500 g (1.10 lbs)
Noryl SE100, Lexan 920A
Noryl SE100, Noryl SE1 GFN3
max. wire cross-section 1.5 mm²
20 ... 253 V AC/DC, 50/60 Hz
12 VA; 7.5 W (10 VA; 5.5 W with Ex)
15x VEGA HART sensors (5x with Ex version)
sensor power supply by VEGASCAN 693
sensors have an own power supply
digital for VEGA HART sensors
approx. 22 V with 15 sensors (60 mA)
approx. 15 V with 5 sensors (20 mA)
approx. 85 mA (approx. 26 mA with Ex)
±10 % of sensor measuring range
0.1 % of sensor measuring range
2-wire screened standard cable
floating spdt
Supplement