Vega VEGASCAN 693 Operating Instructions Manual page 19

15-channel hart signal conditioning instrument
Table of Contents

Advertisement

Device settings - Host Name/
IP addr.
Device settings - Time/Date
Measurement loop - Input
VEGASCAN 693 - 15-channel HART signal conditioning instrument
Setup with the integrated indicating and adjustment unit
For instruments with integrated Ethernet interface also a host
name and the IP address must Subnet Mask for integration in
the network must be entered. These specifications are
available from your network administrator. These settings are
only effective after a restart of VEGASCAN 693.
LAN/Internet
IP address:
192.168.200.200
Subnet mask:
255.255.255.0
Change?
à
Enter the values via the appropriate keys and save your
settings with [OK]. Disconnect briefly the supply voltage so
that the modified settings become effective.
Date and time can be entered in this menu item for instruments
with integrated RS232/Ethernet interface. These time settings
are buffered in case of power failure for approx. 3 days.
Time/Date
8:40
28.09.2004
à
Enter the values via the appropriate keys and save your
settings with [OK].
Because VEGASCAN 693 can read the measured values of
up to 15 sensors (5 with Ex), the individual sensors must be
assigned to the measurement loops. After the addresses of the
HART sensors are assigned, a list with the existing sensors
can be prepared and displayed. Now you can assign the
requested sensor to each measurement loop.
For transmission, VEGASCAN 693 must be informed which
sensor value should be used for further processing. Depend-
ing on the sensor type this can be distance, pressure, interface
or temperature. If a sensor can deliver two measured values,
e.g. pressure and temperature with VEGABAR sensors, a
separate measurement loop must be assigned for each input
variable. When HART sensors of other manufacturers are
connected, the options PV (Primary Value) and SV (Secondary
Value) will be available. The parameter to be transmitted is
stated in the operating instructions manual of the respective
sensor manufacturer.