Setup with the integrated indicating and adjustment unit
Info
Extended settings
24
Note:
When addresses are being assigned, only one sensor with a
particular address must be connected on the bus. If this is not
the case, the sensor cannot be accessed and it is not possible
to assign an address.
Adjust in the menu item "Previous address" the current HART
address of the requested sensor. The default settings of all
supplied VEGA sensors is always 00. After pushing the [->]
key, you can assign in the menu "New address" the requested
HART address in the range of 01 - 15. Make sure that no
address is assigned twice.
Sensor address
New address:
01
In the menu item "Info" the following information is available:
Sensor type and serial number
l
Date of manufacture and software version
l
Date of last change using PC
l
Details of VEGASCAN 693
l
MAC address (with interface option Ethernet)
l
Additional adjustment and diagnostics options are available via
the Windows software PACTware™ and the suitable DTM.
Connection can be made via the interface converter VEGA-
CONNECT or RS232/Ethernet (depending on the instrument
version). Further information is available in chapter "Parameter
adjustment with PACTware™, in the online help of
PACTware™ or the DTM as well as in the operating
instructions manual "RS232/Ethernet connection".