Instrument Repair - Vega VEGASCAN 693 Operating Instructions Manual

15-channel hart signal conditioning instrument
Table of Contents

Advertisement

VEGASCAN 693 - 15-channel HART signal conditioning instrument
?
E036
l
Instrument software not executable (during software
update or after failed update)
à
wait until software update is finished
à
Carry out another software update
?
E053
l
Sensor measuring range not read correctly
à
HART communication error: Check sensor cable and
screening
?
E104
l
Measurement loop deactivated
à
Activate measurement loop (allocation of a sensor to a
measurement loop)

9.3 Instrument repair

If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our homepage
www.vega.com under: "Services – Downloads – Forms and
Certificates – Repair form".
By doing this you help us carry out the repair quickly and
without having to call back for needed information.
Print and fill out one form per instrument
l
Clean the instrument and pack it damage-proof
l
Attach the completed form and possibly also a safety data
l
sheet to the instrument
Please ask the agency serving you for the address of the
l
return shipment