Setup with PACTware™
34
Note:
To adjust with PACTware™ and DTM, a suitable IP address
must be available in the instrument. Each instrument is preset
to address 192.168.200.200. Enter the address and subnet
mask corresponding to your network directly via the keyboard.
Briefly interrupt the power supply, then the instrument is
accessible via its IP address everywhere in the network. In
addition, these specifications must be entered in the DTM (see
chapter "Parameter adjustment with PACTware™").
3
2
Fig. 9: Connection of the PC via Ethernet
1
Ethernet interface of the PC
2
Ethernet connection cable (cross-over cable)
3
Ethernet interface of VEGASCAN 693
4
VEGASCAN 693

7.2 Parameter adjustment with PACTware™

VEGASCAN 693 signal conditioning instrument can be
operated via a Windows PC. You will need the configuration
software PACTware™ and a suitable instrument driver (DTM)
acc. to the FDT standard. In addition, the VEGA DTMs can be
integrated in other frame applications acc. to FDT standard.
For connection either the interface converter VEGACONNECT
or one of the offered interfaces (Ethernet/RS232) in VEGA-
SCAN 693 is required. Not only VEGASCAN 693 itself, but
also connected VEGA HART sensors can be accessed.
VEGASCAN 693 - 15-channel HART signal conditioning instrument