7.4.4
Contact piece replacement (size S10 and S12)
The contact pieces can be replaced in the case of size S10 and S12 contactors. When
replacing for the third time, the arc chamber must be replaced at the same time.
①
②
/
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006
Undo the two screws (hexagon socket-head screws SW4) on the front plate of the contactor
and remove the arc chamber.
7.4 Contact piece replacement (sizes S2 to S12)
Mounting
219