9.4 Surge suppressor
Mounting the 3RT2936-1.... surge suppressor (size S3)
Mounting the 3RT2936-1.... surge suppressor
NOTICE
Danger of material damage
Note the following information when mounting the surge suppressor:
• Temperature when mounting the surge suppressor: > -10 °C
• Maximum opening angle of the cover on the front panel of the contactor: 135°
310
Open the cover on the front panel of the contactor.
Insert the surge suppressor (product version *E03* or higher) into the opening until it engages.
Close the cover on the front panel of the contactor.