Mounting
7.2 Mounting
Screw mounting size S0
The following figure shows the mounting of a contactor of size S0 on a base plate or a panel.
①
182
Screw the contactor tight diagonally into the openings provided using two M4 screws, plain
washers and spring washers.
Maximum tightening torque 1.2 to 1.6 Nm
You can use the 3RT1926-4P screw mounting adapter to make size S0 contactors easier to
mount, if necessary, (e.g. in the case of vertical access when using an insulated screwdriver).
Fit the adapters in the horizontal installation position.
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006