Coupling Relays - Siemens SIRIUS 3RT Manual

Industrial controls, switching devices, contactors / contactor assemblies
Hide thumbs Also See for SIRIUS 3RT:
Table of Contents

Advertisement

Configuration
6.10 Contactors with extended operating range
6.10.2

Coupling relays

Applications
The coupling relays (24 V DC solenoid coil) have been adapted to the specific demands
associated with system-compatible interaction with electronic controls, thanks to their
extended operating range and reduced coil power.
These are versions of the 3RT20/3RH21 contactor ranges, which are characterized by the
following features:
Wide voltage range of the solenoid coil
Coupling
Size
0.7 ... 1.25 x U
relay
version
Switch-
on
power =
holding
power
3RH21
S00
2.8 W at
contactor
24 V
relay
3RT20
S00
2.8 W at
motor
24 V
contactor
S0
4.5 W at
24 V
S2
--
S3
--
Note
The 3RT20/3RH21 coupling relays cannot be expanded by means of auxiliary switch blocks.
116
0.8 ... 1.85 x U
S
Article number
Switch-
on
power =
holding
power
3RH21..-.HB40
1.6 W at
(without RC
24 V
circuit)
3RH21..-.JB40
(with diode)
3RH21..-.KB40
(with
suppressor
diode)
3RT201.-.H.
1.8 W at
(without RC
24 V
circuit)
3RT201.-.J.
(with diode)
3RT201.-.K.
(with
suppressor
diode)
3RT202.-
--
1KB40
(with varistor)
--
--
--
--
0.7 ... 1.20 x U
S
Article number
Switch-
on
power =
holding
power
3RH21..-.MB40-0K
--
T0 (without RC
circuit)
3RH21..-.VB40
(with diode)
3RH21..-.WB40
(with suppressor
diode)
3RT201.-.M.
--
(without RC circuit)
3RT201.-.V.
(with diode)
3RT201.-.S.
(with suppressor
diode)
--
1.0 W at
24 V
--
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006
0.8 ... 1.20 x U
S
Article
Switch-
Article
number
on
number
power =
holding
power
--
--
--
3RT203.-
--
.KB4.
(with
varistor)
--
0.9 W at
3RT204.
24 V
-.KB4.
S

Hide quick links: